INTERFERENCE IMMUNITY ACCORDING TO EN 61000 (INDUSTRY)
Basic standard CE
Electrostatic discharge
EN 61000-4-2
Contact discharge
Air discharge
Comment
Electromagnetic HF field
EN 61000-4-3
Frequency range
Test field strength
Frequency range
Test field strength
Comment
Fast transients (Burst)
EN 61000-4-4
Test voltage
Comment
Surge voltage load (Surge)
EN 61000-4-5
Test voltage L–N
Test voltage L–PE, N–PE
Comment
Power frequency magnetic field immunity
EN 61000-4-8
Test level
Comment
Revision 2-0
Fulfilled requirements according to EN 61000 (CE)
(Interference immunity of industrial environment)
4 kV
8 kV
Criterion B
80 MHz ... 1 GHz
10 V/m
1.4 GHz ... 2 GHz
3 V/m
Criterion A
2 kV
Criterion A
±0.5 kV
±1 kV
Criterion A
30 A/m
Criterion A