Bicker UPSI-1208DPx User Manual page 13

Ups system din-rail
Table of Contents

Advertisement

UPSI-1208DPx
OUTPUT DATA – NORMAL MODE
Unless otherwise stated, all specifications apply to 25 °C ambient temperature,
12 V DC input voltage and nominal output current (I
Output voltage
Output voltage range
Capacitive load
Output current
I
N
I
*
DYN.BOOST
I
SFB
Output power
P
(U
, I
= I
, I
N
N
OUT
N
CHARGE
P
(U
, I
= I
DYN.BOOST
N
OUT
DYN.BOOST
Overcurrent shutdown
Short-circuit proof
No-load proof
OUTPUT DATA – BATTERY MODE
Unless otherwise stated, all specifications apply to 25 °C ambient temperature,
12 V DC input voltage and nominal output current (I
Output voltage
Output voltage range
Output current
I
N
I
*
DYN.BOOST
I
SFB
Output power
P
(U
, I
= I
, I
N
N
OUT
N
CHARGE
P
(U
, I
= I
DYN.BOOST
N
OUT
DYN.BOOST
Overcurrent shutdown
Short-circuit proof
No-load proof
Switching time normal mode > > battery mode
*Max. 58 sec., depending on output power (see for that „F12 Dynamic Powerboost")
Revision 2-0
= 0)
, I
= 0)*
CHARGE
= 0)
, I
= 0)*
CHARGE
).
N
UPSI-1208DP2 / UPSI-1208DP3
12 VDC
U
= U
– 0.6 V DC max. (depending on load)
OUT
IN
3000 µF (at start, 0 A load)
UPSI-1208DP2
8 A
8...10 A
30 A (5 ms)
96 W
96...120 W
8...10 A for max. 58 sec*;
10...10.8 A for max. 100 ms
>10.8 A for max. 5 ms
).
N
UPSI-1208DP2
12 V DC
U
= U
– 0.6 V DC max. (depending on load)
OUT
IN
UPSI-1208DP2
8 A
8...10 A
30 A (5 ms)
91 W
91...114 W
8...10 A for max. 58 sec*;
10...10.8 A for max. 100 ms
>10.8 A for max. 5 ms
<600 µs
UPSI-1208DP3
8 A
8...10 A
30 A (5 ms)
96 W
96...120 W
8...10 A for max. 58 sec*;
10...10.8 A for max. 100 ms
>10.8 A for max. 5 ms
Yes
Yes
UPSI-1208DP2
UPSI-1208DP2
8 A
8...10 A
30 A (5 ms)
91 W
91...114 W
8...10 A for max. 58 sec*;
10...10.8 A for max. 100 ms
>10.8 A for max. 5 ms
Yes
Yes
13