To perform a Loop Booster
output test an access level 3
passcode ( is required.
Select 'Both Sides' to test loop-
powered sounders only (LBMs
are not turned on).
Select 'In Only' to perform test
with loop powered only from the
'Loop Out' end.
Select 'Out Only' to perform
test with loop powered only from
the 'Loop In' end.
997-264-000-10, Issue 10
January 2010
ID50 Series Panel - Operating Manual
Test Loop Booster Outputs
A number of tests are available to satisfactorily test the
operation of the Loop Booster Modules (LBMs) during
alarm conditions. The tests are designed so that the power
delivered to the loop by the panel can be switched off from
either end, or each LBM in turn can be prevented from
being turned on. The tests are designed, when combined
with a walk-test, to check that:
a. The panel operates all loop-powered devices correctly
with the LBM(s) with one source of loop power isolated.
b. All loop-powered outputs operate correctly with any individual
LBM disabled or with the loop only powered from one end.
[U0 Outputs]
1 Press the '
the Loop Booster test procedure. With the panel currently
at access level 2, the following warning is displayed
prompting for entry of access level 3 passcode:
COMMISSION MODE ACCESS
Enter Level 3 passcode -
2 Having entered the access level 3 passcode, press
the '
5
[LBM Test]
: Start
3 Before the test starts a 0% percentage indication of the
equipment under test is displayed on the top line. As the test
progresses, the percentage value increases to 100% as to
indicate that all loop-powered devices under test are operating
correctly. This percentage value may go down if a device
starts reporting incorrectly or becomes de-activated.
[LBM Test]
: Start
4 Press the '
Booster options: 'In Only' or 'Out Only'
[LBM Test]
: Start
[LBM Test]
: Start
5 To perform a loop test without loop booster support
you can turn off individual LBMs while testing that loop-
powered sounders are still able to operate correctly.
[LBM Test]
: Start
6 Press the
the Test Menu.
Note: If the test is not cancelled manually, it is cancelled
automatically 4 hours after the last panel keystroke.
26
1:Internal
3:Loop Power
' button on the numeric keypad to select
3
< BackSp
' button to start the test.
Loop : Both Sides
: Change<:Exit
Loop : Both Sides
: Change<:Exit
/
' pushbuttons to select the other Loop
2
8
Loop : In Only
: Change<:Exit
Loop : Out Only
: Change<:Exit
M nn : Inactive
: Change<:Exit
' button to cancel the test and return to
4
2:SLC
0%
0%
0%
0%
0%

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier id50 series

Table of Contents