Location Requirements & Considerations - Maytag Amana CVC96 Series Installation Instructions Manual

Two-stage gas furnace
Table of Contents

Advertisement

Return air ducts are provided and sealed to the furnace.
A return air temperature range between 60ºF (16ºC) and 80ºF (27ºC) is maintained.
Air filters are installed in the system and replaced daily during construction and upon completion of construction.
The input rate and temperature rise are set per the furnace rating plate.
The furnace must be installed as a two pipe system, using 100% outside air for combustion during construction.
The furnace heat exchanger, components, duct system, air filters and evaporator coils are thoroughly cleaned following final
construction clean up by a qualified person.
All furnace operating conditions (including ignition, input rate, temperature rise and venting) are verified by a qualified
person according to these installation instructions.
Furnace doors must be in place on the furnace while the furnace is operating in any mode.
Damage or repairs due to failure to comply with these requirements are not covered under the warranty.
NOTE: The Commonwealth of Massachusetts requires that the following additional requirements must also be met:
Gas furnaces must be installed by a licensed plumber or gas fitter.
A T-handle gas cock must be used.
If the unit is to be installed in an attic, the passageway to and the service area around the unit must have flooring.
To ensure proper furnace operation, install, operate and maintain the furnace in accordance with these installation and
operation instructions, all local building codes and ordinances. In their absence, follow the latest edition of the National Fuel Gas
Code (NFPA 54/ANSI Z223.1), and/or CAN/CSA B149 Installation Codes, local plumbing or waste water codes, and other applicable
codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI Z223.1) can be obtained from any of the following:
The rated heating capacity of the furnace should be greater than or equal to the total heat loss of the area to be heated. The total
heat loss should be calculated by an approved method or in accordance with "ASHRAE Guide" or "Manual J-Load Calculations"
published by the Air Conditioning Contractors of America.
L
R
OCATION
EQUIREMENTS
Follow the instructions listed below and the guidelines provided in the Combustion and Ventilation Air Requirements section when
selecting a furnace location.
Centrally locate the furnace with respect to the proposed or
existing air distribution system.
Ensure the temperature of the return air entering the furnace
is between 55°F and 100°F when the furnace is heating.
Provide provisions for venting combustion products outdoors
through a proper venting system. Special consideration
should be given to vent/flue pipe routing and combustion
air intake pipe when applicable. Refer to Vent/Flue Pipe
and Combustion Air Pipe -Termination Locations for
appropriate termination locations and to determine if the
American National Standards Institute
25 West 43rd Street, 4th Floor
New York, NY 10036
National Fire Protection Association
Quincy, MA 012169-7471
8501 East Pleasant Valley
Independence, OH 44131
A copy of the CAN/CSA B149 Installation Codes can also be obtained from:
Etobicoke, Ontario, Canada M9W 1R3
& C
ONSIDERATIONS
1 Batterymarch Park
CSA International
CSA International
178 Rexdale Boulevard
T
O PREVENT POSSIBLE EQUIPMENT DAMAGE
PERSONAL INJURY OR DEATH
OBSERVED WHEN INSTALLING THIS UNIT
P
OSSIBLE PROPERTY DAMAGE
,
FIRE
EXPLOSION
OR CARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION
REPAIR OPERATION
6
WARNING
,
PROPERTY DAMAGE
,
THE FOLLOWING BULLET POINTS MUST BE
.
WARNING
,
PERSONAL INJURY OR DEATH DUE TO
,
,
,
SMOKE
SOOT
CONDENSATION
,
OR MAINTENANCE OF THIS PRODUCT
,
,
ELECTRICAL SHOCK
,
.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Amana mvc96 seriesAmana gmvc96

Table of Contents