SE10000H-
SE3000H-US SE3800H-US SE5000H-US SE6000H-US SE7600H-US
SE11400H-US
Unit
US
Nighttime Power
< 2.5
W
Consumption
ADDITIONAL FEATURES
Supported
RS485, Ethernet, ZigBee (optional), Cellular (Optional)
Communication Interfaces
Revenue Grade Data, ANSI
(1)
Optional
C12.20
Inverter Commissioning
with the SetApp mobile application using built-in Wi-Fi access point for local connection
Rapid Shutdown - NEC
Automatic Rapid Shutdown upon AC Grid Disconnect
2014 and 2017 690.12
STANDARD COMPLIANCE
Safety
UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07
Grid Connection Standards 
IEEE1547, Rule 21, Rule14 (HI)
Emissions
FCC part15 class A
RoHS
Yes
INSTALLATION SPECIFICATIONS
AC output conduit size /
1" minimum / 14 - 6 AWG
1" minimum / 14-4 AWG
AWG range
DC input conduit size / #
1" minimum / 1-3 strings /
1" minimum / 1-2 strings / 14-6 AWG
of strings / AWG range
14-6 AWG
Dimensions with Safety
21.3 x 14.6 x 7.3 / 540 x 370
17.7 x 14.6 x 6.8 / 450 x 370 x 174
in/mm
Switch (HxWxD) 
x 185
(1) Inverter with Revenue grade meter P/N: SExxxxH-US000BNC4; Inverter with Revenue grade and Export/Import meter P/N: SExxxxH-US000BNI4