Chapter 4
[Hd102]~[Hd118]
(SM/PMM) basic parameters
Code/Name
Range (unit)
Hd102
Sync.
0.01~630.00
Motor capacity
(kW)
setting, 1st-motor
Hd103
Sync.
2~48(Pole)
Motor capacity
setting, 1st-motor
Hd104
Sync.
10.00~590.00
Base frequency
(Hz)
setting, 1st-motor
Hd105
Sync.
10.00~590.00
Maximum
(Hz)
frequency setting,
1st-motor
Hd106
Sync.
1~1000
Motor rated
(V)
voltage, 1st-motor
Hd108
Sync.
0.01~10000.00
Motor rated
(A)
current, 1st-motor
Code/Name
Hd110
Sync. Motor
Constant R, 1st-motor
Hd112
Sync. Motor
Constant Ld, 1st-motor
Hd114
Sync. Motor
Constant Lq, 1st-motor
Hd116
Sync. Motor
Constant Ke, 1st-motor
Hd118
Sync. Motor
Constant J, 1st-motor
・Motor capacity and number of poles will be set by
Hitachi characteristics table
・For SM/PMM, frequency, voltage, and the motor
characteristics are necessary.
・If the maximum current is decided, sets with a margin
the overcurrent detection level [bb160].
Motor typical data
Code
[Hd102]
Capacity
[Hd103]
Number of poles
[Hd104]
Frequency
[Hd105]
[Hd106]
Voltage
Current
[Hd108]
※ Initial value depends on the inverter.
・If motor capacity [Hd102], number of poles [Hd103] are
changed, the motor characteristics are set according to
the internal Hitachi table values.
・By auto-tuning at stop, values of [Hd110]~[Hd114]
can be acquired.
Initial value
Factory setting
4
60.00(JPN)(USA)/
50.00(EU)(ASIA)(CHN)
60.00(JPN)(USA)/
50.00(EU)(ASIA)(CHN)
(200V Class)
200(JPN)
230(EU)(USA)(ASIA)(CHN)
(400V Class)
400(JPN)(EU)(ASIA)(CHN)
460(USA)
Factory setting
Initial
Range (unit)
value
0.000001~
Factory
1000.000000 (Ω)
setting
0.000001~
Factory
1000.000000 (mH)
setting
Factory
0.000001~
1000.000000 (mH)
setting
Factory
0.1~100000.0
setting
(mVs/rad)
0.00001~
Factory
setting
10000.00000 (kgm2)
Range of values (unit)
0.01~630.00 (kW)
2~48 (Poles)
10.00~590.00 (Hz)
10.00~590.00 (Hz)
1~1000 (V)
0.01~10000.00 (A)
For parameter configuration
Minimum frequency settings
Code/Name
Hd130
Minimum Frequency for
Sync.M, 1st-motor
Hd131
No-Load current for
Sync.M, 1st-motor
・By base frequency[Hd104]×[Hd130], change from Sync.
to sensorless is possible.
・By [Hd131], the sensorless vector control no-load
current is set.
Magnetic pole position estimation SM(PMM)
Code/Name
Hd132
Starting Method for
Sync.M, 1st-motor
Hd133
IMPE 0V wait number for
Sync.M, 1st-motor
Hd134
IMPE detect wait
number for Sync.M, 1st-motor
Hd135
IMPE detect number for
Sync.M, 1st-motor
Hd136
IMPE voltage gain for
Sync.M, 1st-motor
Hd137
IMPE Mg-pole position
offset, 1st-motor
・By setting [Hd132] to initial position estimate, it will
estimate the pole position, for next runs will use the
saved position, unless it gets disconnected
・Offset [Hd137] is added at the first start when doing
reverse motion.
IVMS setting
Code/
Hd-41
Carrier frequency at IVMS
Hd-42
Filter gain of current
detection at IVMS
Hd-43
VMS P-Gain for speed
control, SM(PMM)-IVMS
Hd-44
Open phase switching
threshold compensation
Hd-45
P gain for speed control
SM(PMM)-IVMS
Hd-46
I gain for speed control
SM(PMM)-IVMS
Hd-47
IVMS Wait time for open
phase switching
Hd-48
Limitation of decision about
the drive direction, SM(PMM)-IVMS
Hd-49
open phase voltage detection
timing adjustment, SM(PMM)-IVMS
Hd-50
Minimum pulse width
adjustment, SM(PMM)-IVMS
Hd-51
IVM threshold current limit
Hd-52
IVMS threshold gain
・Above parameters are for adjustment in SM(PMM) driving with
IVMS
4-51
[Hd130]~[Hd218]
Initial
Range (unit)
value
8
0~50(%)
10
0~100(%)
Initial
Range (unit)
value
00(Synchronous)/
01(Initial position
00
estimate)
0~255
3
0~255
3
0~255
10
0~200(%)
100
0~359(°)
15
Initial
Range(unit)
Value
2.0
0.5~16.0(kHz)
0~1000
100
00,01,02,03
00
00(disable)/01(enable)
00
0~1000
100
100
0~10000
100
0~1000
00(disable)/01(enable)
00
0~1000
10
0~1000
100
0~255
100
0~255
100