Chapter 4
[Input terminal function list]
Functio
Symb
Function
n code
ol
name
000
no
Not use
001
FW
Forward rotation
002
RV
Reverse rotation
Multi speed
003
CF1
selection 1
Multi speed
004
CF2
selection 2
Multi speed
005
CF3
selection 3
Multi speed
006
CF4
selection 4
007
SF1
Multi speed Bit-7
008
SF2
Multi speed Bit-2
009
SF3
Multi speed Bit-3
010
SF4
Multi speed Bit-4
011
SF5
Multi speed Bit-5
012
SF6
Multi speed Bit-6
013
SF7
Multi speed Bit-6
Trigger for
014
ADD
frequency
addition[Ab105]
SCH
Speed reference
015
G
change
016
STA
3-wire Start
017
STP
3-wire Stop
Forward Over
018
FR
Travel
analog command
019
AHD
holding
Remote control
020
FUP
Speed-UP
function
Remote control
021
FDN
Speed-DOWN
function
Remote control
022
UDC
data clearing
023
F-OP
Force operation
2nd-motor
024
SET
control
028
RS
Reset
029
JG
Jogging
External Dynamic
030
DB
brake
2-step
031
2CH
Acceleration/Dec
eleration
032
FRS
Free run stop
033
EXT
External fault
unattended
034
USP
start protection
Commercial
035
CS
Supply change
SFT
036
Soft-Lock
BOK
037
Answer back
from Brake
Description
-
Activating (ON) only one of them
will grant forward or reverse
rotation command. ⇒ [AA111]
Changing the states of these
terminals, allows to set different
motor speeds and change among
them.
⇒[Ab110]~[Ab-25],
[Ab210]
When is turned ON, adds the
specified frequency value.
⇒[AA106]
Main speed(OFF)/Sub-speed (ON),
to change between them use ⇒
[AA105].
If [STA] is ON, start the motor. If
[STP] is ON stop the motor.
Forward operation direction if [FR]
is (OFF), reverse operation direction
if is (ON).
⇒[AA111]
When the Analog inputs Ai1,2,3 are
in use, if AHD terminal is in ON
state, holds the Analog terminal
value.
⇒[AA101]
If the frequency can be set ([AHD]
ON included), [FUP] ON accelerates,
and [FDN] ON decelerates. [UDC]
returns to the saved value. ⇒
[CA-62]~[CA-66]
If ON, switch set parameters.
⇒[CA-68],[CA-69]
Change between 1st-motor (OFF)
and 2nd-motor (ON).
⇒By parameter
Reset trip⇒[CA-61],[bb-41]
Activates Jogging operation.
⇒[AG-20],[AG-21]
Enables the DC braking operation⇒
[AF101]~[AF109]
If ON, changes the Acc/Decel time.
⇒[AC115]
If ON allows the motor to free run.
⇒[AA115],[bb-40]
If ON error E012 occurs.
⇒Trip E012
ON if at the start-up, the RUN
command was issued right at the
start up, E013 error.
⇒Tripping E013
When changing to the public
electric grid, if it is ON, will cut the
output.
If ON, disables parameter changes.
⇒[UA-21]
Here
is
inputted
the
brake
confirmation signal for the brake
control.
For parameter configuration
Function
Symbol Function name
code
Accumulation
038
OLR
input power
clearance
Accumulation
039
KHC
output power
clearance
Disable PID1
040
OKHC
PID1
integration
041
PID
reset
Disable PID2
042
PIDC
PID2
integration
043
PID2
reset
Disable PID3
044
PIDC2
PID3
integration
046
PID3
reset
Disable PID4
046
PIDC3
PID4
integration
047
PID4
reset
Multi set-point
048
PIDC4
selection 1
Multi set-point
051
SVC1
selection 2
Multi set-point
052
SVC2
selection 3
Multi set-point
053
SVC3
selection 4
054
SVC4
PID gain change
PID output
055
PRO
switching 1
PID output
056
PIO
switching 2
SLEEP condition
ativation
057
PIO2
WAKE condition
058
SLEP
ativation
Torque limit
059
enable
WAKE
Torque limit
060
TL
selection bit 1
Torque limit
061
TRQ1
selection bit 2
Accumulation
062
TRQ2
input power
clearance
4-36
[Input terminal function list]
Description
Switches between Overload limit
1(OFF) and 2(ON).
⇒[bA122]~[bA128]
If ON, clears the Accumulated input
power monitor.
⇒[UA-14]
If ON, clears the Accumulated
output power monitor.
⇒[UA-12]
If ON, disables PID1 and changes
the PID target value for the
frequency reference.
⇒[AH-01]
If ON, clears the integral value of
the control.
⇒[AH-62],[AH-65]
If ON, disables PID2 and changes
the PID target value for the
frequency reference.
⇒[AJ-01]
If ON, clears the integral value of
the control. ⇒[AJ-14]
If ON, disables PID3 and changes
the PID target value for the
frequency reference.
⇒[AJ-21]
If ON, clears the integral value of
the control. ⇒[AJ-34]
If ON, disables PID4 and changes
the PID target value for the
frequency reference.
⇒[AJ-41]
If ON, clears the integral value of
the control. ⇒[AJ-54]
The target value can be selected by
changing the pattern of ON/OFF
states.
⇒[AH-06]
Switches between Gain 1(OFF) and
Gain 2(ON).
Switches PID Output 1 to 4 by
(PIO1:PIO2).
PID1 Enable(OFF:OFF)
PID2 Enable(OFF:ON)
PID3 Enable(ON:OFF)
PID4 Enable(ON:ON)
In case it is used in Sleep terminal
functions, when ON, it activates. ⇒
[AH-85]
In case it is used in Wake terminal
functions, when ON, it activates. ⇒
[AH-93]
If ON, enables torque limit.
The target value can be selected by
changing the pattern of ON/OFF
states.