Chapter 4
[CC-20]~[CC-33]
Output terminal response
Code/Name
CC-20
Output terminal [11] on-delay time
CC-21
Output terminal [11] off-delay time
CC-22
Output terminal [12] on-delay time
CC-23
Output terminal [12] off-delay time
CC-24
Output terminal [13] on-delay time
CC-25
Output terminal [13] off-delay time
CC-26
Output terminal [14] on-delay time
CC-27
Output terminal [14] off-delay time
CC-28
Output terminal [15] on-delay time
CC-29
Output terminal [15] off-delay time
CC-30
Output terminal [16] on-delay time
CC-31
Output terminal [16] off-delay time
CC-32
Output terminal [AL] on-delay time
CC-33
Output terminal [AL] off-delay time
・Sets the delay time since the output terminal changes,
until it actually become responsive.
Function
code
Initial
Range (unit)
value
0.00
0.00
100.00(s)
0.00
100.00(s)
0.00
0.00
0.00
100.00(s)
0.00
100.00(s)
0.00
0.00
0.00
100.00(s)
0.00
100.00(s)
0.00
0.00
0.00
100.00(s)
0.00
0.00
100.00(s)
0.00
100.00(s)
0.00
0.00
0.00
100.00(s)
0.00
100.00(s)
0.00
0.00
0.00
100.00(s)
0.00
100.00(s)
0.00
0.00
100.00(s)
0.00
4-40
For parameter configuration
[Intelligent output terminal function list]
Symbol
Function name
000
no
Not use
001
RUN
Running
Constant-speed
002
FA1
reached
Set speed
003
FA2
overreached
Set frequency
004
FA3
reached
Set speed
005
FA4
overreached 2
006
FA5
Set speed reached
007
IRDY
inverter ready
008
FWR
Forward rotation
009
RVR
Reverse rotation
Speed referenc =
010
FREF
Keypad is selected
Run command =
011
REF
Keypad is selected
2nd control is
012
SETM
selcted
016
OPO
Option output
017
AL
Alarm
018
MJA
Major failure
019
OTQ
Over-torque
Instantaneous
020
IP
power failure
021
UV
Undervoltage
022
TRQ
Torque limited
IP-Non stop function
023
IPS
is active
Accumulated
024
RNT
operation time over
Accumulated
025
ONT
power-on time over
Electronic thermal
026
THM
alarm signal(MTR)
Electronic thermal
027
THC
alarm signal(CTL)
Capacitor life
029
WAC
warning
Cooling-fan speed
030
WAF
drop
Starting contact
031
FR
signal
Heat sink overheat
032
OHF
warning
Low-current
033
LOC
indication signal
Low-current
034
LOC2
indication signal 2
Overload notice
035
OL
advance signal (1)
Overload notice
036
OL2
advance signal (2)
037
BRK
Brake release
038
BER
Brake error
039
CON
Contactor control
Description
While output is active
When
constant
speed
reached, ON
ON at reaching the specified
frequency or more
ON only at reaching the
specified frequency
ON at reaching the specified
frequency 2 or more
ON only at reaching the
specified frequency 2
ON when inverter is ready
ON while in forward drive
ON while in reverse drive
ON
if
the
frequency
reference is from keypad
ON
if
the
motion
operation
is
from
operation keypad
ON if 2nd-motor selected
Controlled by the Option
ON when trip happens
ON if major failure trips
ON if torque is exceeded
ON if control power drops
ON if main voltage drops
ON if torque limit operates
ON if set in power loss
ON if set time is exceeded
ON if set time is exceeded
ON
if
motor
thermal
integral value exceeds set
value
ON if inverter thermal
integral value exceeds set
value
ON by life warning
ON by life warning
On while in operation
ON when the heatsink is
overheated.
ON if output current is less
that the specified value
ON if output current is less
that the specified value
ON if output current
exceeds specified value
ON if output current
exceeds specified value
ON when brake releases
ON if abnormality in
sequence happens
ON if contactor releases