Chapter 5
Code
Details
・ Ground fault detected at main
E014
circuit voltage turning-on
・ Continued state of incoming high
E015
power
・ Instantaneous power failure,
E016
control supply has dropped
・ Abnormality in temperature
E019
detector circuit
・ Because of cooling-fan life span,
E020
internal temperature has raised
・ Internal temperature has
E021
increased
・ Disconnection of the wiring in the
E024
supply side has occurred
・ Suddenly current increase
E030
・ Disconnection of the wiring in the
E034
motor side has occurred
・ Abnormal motor temperature
E035
・ Thermistor abnormality
・ Brake abnormality
E036
・ During slow speed, current has
E038
increased
・ Panel disconnection error
E040
・ RS485 communication error
E041
・ RTC error
E042
E043
・ There is an error in the EzSQ
E045
E050
programme.
E059
E060
・ There is an error in the option.
E089
E090
・ There is an error in the STO path.
E093
※For others errors not shown above, refer to the user's
guide.
Warning events
※Regarding the warnings, please refer to the user's guide.
Fixing the parameter details shown in the panel screen
may end the warning
Corrective actions
・ Check for ground fault of the motor, wiring, etc.
・ Review the power circumstances, such as the power
supply capacity
・ If you wish to avoid the tripping, use the power loss retry
function.
・ Carry out counter measures for the inverter noise
・ Consecutive errors may cause a failure
・ Change of the cooling-fan is necessary
・ Lower the carrier frequency
・ Requires a review of the installation circumstances
・ Lower the carrier frequency
・ Check the fastening of the input wiring with screws
・ Check that the 3 phases are correctly inserted
・ Output wiring ground fault ・ Disconnection confirm
・ Check that the motor is not locked
・ Check the output wiring disconnection, motor insulation
failure, ...etc.
・ Check that the 3 phases are correctly inserted
・ Improve the motor cooling circumstances
・ Use the overload restriction function
・ Check for the break-down of the thermistor
・ Check the thermistor settings
・ Check for the break-down of the brake and for the
disconnection of the wiring for the [BOK] signal
・ Check the brake waiting time
・ If torque is needed during slow speed, a review of the
inverter capacity is necessary
・ Check for the disconnection of the panel from the
inverter
・ Noise counter-measures are necessary
・ Noise counter-measures are necessary
・ Check the communication setting
・ Battery replacement for the panel is necessary
・ For more information, please refer to the user's guide.
・ For more information, please refer to each option in
user's guide.
・ For more information, please refer to the P1 functional
safety guide.
5.2 Confirming the status
■Frequently asked questions – FAQ (simplified edition)
Details of display
5-2
Troubleshooting
Related parameter
-
[dA-40]
[bb-20]
-
-
-
[bb101]
-
[bb101]
-
-
-
-
-
-
-
[bA122]
-
[Cb-40]
[dA-51]
[AF134][AF141]
-
[UA-20]
-
-
[CF-01]
-