Table 10. Troubleshooting methods (continued)
Symptom
Humidifier Inoperative
Note: See humidifier manual for additional help.
AH-SVX008C-EN
Probable Cause
a. Water supply has been turned off or not
connected.
b. Humidifier switch is in "Off" position.
c. Electrical connections are loose.
d. Humidifier fuses are blown.
e. Relative humidity is above setpoint.
f. Yellow status LED is flashing.
g. Water conductivity is too low.
Recommendation
Connect and/or turn on water supply.
Turn switch to "Auto/On" position.
Tighten electrical connections.
Check for overcurrent by the humidifier
electrodes. Drain water from tank and refill.
Replace fuses.
Adjust humidistat setpoint.
Consult humidifier manual.
Add a teaspoon of table salt to the water through
the top of the cylinder. Typically only required on
initial start-up.
Maintenance
43