Thermo Scientific TSC Series User Manual page 51

-40c and -86c
Table of Contents

Advertisement

Section 7
Specifications
Number (Model)
Temperature Range
Exterior Dimensions
Interior Dimensions
Capacity
Refrigeration
Insulation
Electrical -
nominal voltage ±10%
Breaker Requirements
Shipping Weight
Number (Model)
Temperature Range
Exterior Dimensions
Interior Dimensions
Capacity
Refrigeration
Insulation
Electrical -
nominal voltage ±10%
Breaker Requirements
Shipping Weight
7-2
TSC Series
TSC1790A (8769)
-50°C (-58°F) to -86°C (-123°F) in an 18C to 32C * (64.4F to 89.6F) ambient
87.6.0"W x 40.5" H x 33.8" F-B
(222.5cm x 102.9cm x 85.9cm)
Add 7.9" (20.1cm) to F-B for wall spacer/handle.
58.8"W x 28.0"H x 18.5" F-B
(149.4cm x 71.1cm x 47.0cm)
17.0 cu. ft. (481.4 liters)
Cascade system, (2) hermetically-sealed compressors
Non CFC, foamed-in-place urethane: 5.0" (12.7cm) cabinet; 2.0" (5.0cm) lid; 1.0" (12.5cm) sub-lids
120VAC, 1 PH, 60 Hz, 16.0 FLA
Operating Range: 108VAC-130VAC
20 Amp Dedicated Circuit,
20 Amp Time Delay Breaker
821 lbs. (372kg)
TSC2090V (8772)
-50°C (-58°F) to -86°C (-123°F) in an 18C to 32C * (64.4F to 89.6F) ambient
96.0"W x 40.5" H x 33.4" F-B
(243.8cm x 102.9cm x 84.8cm)
Add 7.9" (20.1cm) to F-B for wall spacer/handle.
66.5"W x 28.0"H x 18.5" F-B
(168.9cm x 71.1cm x 47.0cm)
20.0 cu. ft. (566.3 liters)
Cascade system, (2) hermetically-sealed compressors
Non CFC, foamed-in-place urethane: 5.0" (12.7cm) cabinet; 2.0" (5.0cm) lid; 1.0" (12.5cm) sub-lids
230VAC, 1 PH, 50 Hz, 12.0 FLA
Operating Range: 208VAC-240VAC
15 Amp Dedicated Circuit,
15 Amp Time Delay Breaker
833 lbs. (378kg)
TSC1790V (8770)
230VAC, 1 PH, 50 Hz, 12.0 FLA
Operating Range: 208VAC-240VAC
15 Amp Dedicated Circuit,
15 Amp Time Delay Breaker
TSC2090D (8773)
208-230VAC, 1 PH, 60 Hz, 12.0 FLA
Operating Range: 208VAC-240VAC
15 Amp Dedicated Circuit,
15 Amp Time Delay Breaker
TSC1790D (8771)
208-230VAC, 1 PH, 60 Hz, 12.0 FLA
Operating Range: 208VAC-240VAC
15 Amp Dedicated Circuit,
15 Amp Time Delay Breaker
TSC2090A (8774)
120VAC, 1 PH, 60 Hz, 16.0 FLA
Operating Range: 108VAC-130VAC
20 Amp Dedicated Circuit,
20 Amp Time Delay Breaker
Thermo Scientific

Advertisement

Table of Contents
loading

Table of Contents