Preparation Before Installation; Installation Of Indoor Unit - Daikin FCQ24TAVJU Installation Manual

Hide thumbs Also See for FCQ24TAVJU:
Table of Contents

Advertisement

4. PREPARATION BEFORE INSTALLATION

(1) Check the relation of location between the ceiling
opening and the indoor unit suspension bolts.
5 Suspension bolt pitch
3 Indoor unit
2 Ceiling opening
1 Decoration panel
Fig. 4
1
37-3/8 (950)
2
33-7/8 – 35-7/8 (860 – 910)
3
33-1/16 (840)
4
30-3/4 (780)
5
28 (710)
Ceiling
View as seen from A
Fig. 5
Decoration Panel
BYCQ125B-W1
4-15/16 – 5-1/8
in. (mm)
(125 – 130)
CAUTION
Reduce the distance between the unit and ceiling to
1-3/8 in. (35 mm) or below in order to maintain an over-
lapping panel margin 13/16 in. (20 mm) for the opening
on the ceiling. If the distance exceeds 1-3/8 in. (35 mm),
attach ceiling material to the part marked
the ceiling. (Refer to Fig. 6)
English
Refrigerant
piping
Suspension
bolt (×4)
A
[unit: in. (mm)]
Hanger
BYCQ125BGW1
8-1/16 – 8-1/4
(205 – 210)
or replace
Frame
Ceiling
material
≤1-3/8 (35)
≥13/16
(20)
33-7/8 to 35-7/8 (860 – 910)
(Ceiling-opening dimension)
Fig. 6
(2) Make the ceiling opening required for installation.
• Use the installation pattern paper (5) matched to the
ceiling opening dimension.
• Make the ceiling opening required for installation at
the installation location and carry out refrigerant/drain
piping, power supply wiring, remote controller wiring
(not needed in case of wireless remote con troller) and
wiring between the indoor and outdoor units. (Refer
to each section 6. REFRIGERANT PIP I NG WORK,
7. DRAIN PIPING WORK and 8. ELECTRIC WIRING
WORK)
• After making the opening, sometimes it is necessary
to reinforce the ceiling framework to maintain a level
ceiling and prevent it from vibrating.
For details, consult with the builder and interior de-
signer.
(3) Install the suspension bolts.
• User either a M8-M10 size bolt or equipment.
• Use hole-in-anchors for the existing bolts and embed-
ded inserts or foundation bolts for new bolts, and fix the
indoor unit firmly to the building so that it may withstand
the mass of the unit.
In addition, adjust clearance (2 – 4 in. (50 – 100 mm))
from the ceiling in advance.
<Installation examples>
Note) The above shown parts are all field supply.

5. INSTALLATION OF INDOOR UNIT

<<It is easy to attach the optional parts (except for deco-
ration panel) before installing the indoor unit. Refer to
also the installation manual attached to the optional
parts.>>
For installation, use the attached installation parts and
specified parts.
[Install the indoor unit in the order of steps (1), (2), (3), (4), (5),
and (6) in case of a newly built ceiling, or in the order of steps
(1), (3), (4), and (5) in case of an existing ceiling.]
[unit: in. (mm)]
≤1-3/8 (35)
≥13/16
(20)
(Ceiling-panel
overlapping
dimension)
Ceiling slab
Foundation bolt
Long nut or turn-buckle
Suspension bolt
Ceiling surface
4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fcq18tavjuFcq30tavjuFcq36tavjuFcq42tavjuFcq48tavju

Table of Contents