Daikin FCQ18PAVJU Installation Manual
Daikin FCQ18PAVJU Installation Manual

Daikin FCQ18PAVJU Installation Manual

Split system air conditioners
Hide thumbs Also See for FCQ18PAVJU:

Advertisement

SPLIT SYSTEM Air Conditioners
MODELS
Ceiling mounted cassette type (Round flow model)
FCQ18PAVJU
FCQ24PAVJU
FCQ30PAVJU
FCQ36PAVJU
FCQ42PAVJU
Read these instructions carefully before installation.
Keep this manual in a handy place for future reference.
Lire soigneusement ces instructions avant l'installation.
Conserver ce manuel à portée de main pour référence
ultérieure.
Lea cuidadosamente estas instrucciones antes de instalar.
Guarde este manual en un lugar a mano para leer en caso
de tener alguna duda.

INSTALLATION MANUAL

English
Français
Español

Advertisement

Table of Contents
loading

Summary of Contents for Daikin FCQ18PAVJU

  • Page 1: Installation Manual

    INSTALLATION MANUAL SPLIT SYSTEM Air Conditioners MODELS Ceiling mounted cassette type (Round flow model) FCQ18PAVJU FCQ24PAVJU English FCQ30PAVJU FCQ36PAVJU FCQ42PAVJU Français Español Read these instructions carefully before installation. Keep this manual in a handy place for future reference. Lire soigneusement ces instructions avant l’installation.
  • Page 2: Table Of Contents

    SPLIT SYSTEM Air Conditioners Installation manual CONTENTS 1. SAFETY CONSIDERATIONS..................1 2. BEFORE INSTALLATION....................3 3. SELECTING INSTALLATION SITE ................6 4. PREPARATIONS BEFORE INSTALLATION ..............7 5. INDOOR UNIT INSTALLATION..................9 6. REFRIGERANT PIPING WORK .................. 10 7. DRAIN PIPING WORK ....................13 8.
  • Page 3 • Do not change the setting of the protection devices. If the pressure switch, thermal switch, or other pro- tection device is shorted and operated forcibly, or parts other than those specified by Daikin are used, fire or explosion may occur.
  • Page 4: Before Installation

    • Refrigerant R410A in the system must be kept clean, dry, and tight. (a) Clean and Dry -- Foreign materials (including mineral oils such as SUNISO oil or moisture) should be prevented from getting into the system. (b) Tight -- R410A does not contain any chlorine, does not destroy the ozone layer, and does not reduce the earth’s protection again harmful ultraviolet radiation.
  • Page 5 1. PRECAUTIONS • Be sure to read this manual before installing the indoor unit. • When selecting installation site, refer to the paper pattern. • This unit is suitable for installation in a household, commercial and light industrial environment. • Do not install or operate the unit in rooms mentioned below. •...
  • Page 6 3. OPTIONAL ACCESSORIES • The optional decoration panel and remote controller are required for this indoor unit. (Refer to Table 1, 2) (However, the remote controller is not required for the slave unit of a simultaneous operation system.) Table 1 Unit model Optional decoration panel BYCP125K-W1...
  • Page 7: Selecting Installation Site

    Points for explanation about operations The items with WARNING and CAUTION marks in the operation manual are the items per- taining to possibilities for bodily injury and material damage in addition to the general usage of the product. Accordingly, it is necessary that you make a full explanation about the described con- tents and also ask your customers to read the operation manual.
  • Page 8: Preparations Before Installation

    CAUTION • The indoor and outdoor units and the power supply wiring and remote controller wire must be installed at least 40in. away from any televisions or radios. This is to prevent interference with picture and sound reception. (Interference may occur even at 40in. away depending on the reception quality.) (2) Ceiling height This product can be installed in ceilings up to 11-1/2ft.
  • Page 9 Installation is possible when ceiling opening dimensions is as follows • When installing the unit within the frame for fixing false ceiling. 33-7/8 (Unit: in.) (Opening dimension inside the flame for ceiling) Frame False ceiling ≥13/16 ≥13/16 33-7/8 – *35-7/8 33-1/16 (Ceiling opening dimension) (Ceiling-panel...
  • Page 10: Indoor Unit Installation

    5. INDOOR UNIT INSTALLATION Installing optional accessories (except for the decoration panel) before installing the indoor unit is easier. However, for existing ceilings, install fresh air inlet component kit and branch duct before installing the unit. As for the parts to be used for installation work, be sure to use the provided accessories and specified parts designated by our company.
  • Page 11: Refrigerant Piping Work

    <Ceiling work> (1-3) Adjust the unit to the right position for installation. (Refer to “4. PREPARATIONS BEFORE INSTALLATION-(1)”.) • Using the Installation guide (15) allows you to check the positions from the underside of the unit to the lower ceiling surface. Apply the short side of the cut-out section.
  • Page 12 CAUTION • Use a pipe cutter and flare suitable for the type of refrigerant. • Apply ester oil or ether oil around the flare section before connecting. • To prevent dust, moisture or other foreign matter from infiltrating the tube, either pinch the end or cover it with tape.
  • Page 13 Not recommendable but in case of emergency You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may follow the installation method mentioned below. When you keep on tightening the flare nut with a spanner, there is a point where the tightening torque suddenly increases.
  • Page 14: Drain Piping Work

    CAUTION CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING “Do not use flux when brazing refrigerant piping. Therefore, use the phosphor copper brazing filler metal (BCuP-2/B-Cu93P-710/795) which does not require flux.” (Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil.) •...
  • Page 15 • Make sure that heat insulation work is executed on the following 2 spots to prevent any possible water leak- age due to dew condensation. • Indoor drain pipe • Drain socket Metal Metal Large sealing pad (10) clamp (2) clamp (2) (accessory) (accessory)
  • Page 16 WHEN ELECTRIC WIRING WORK IS FINISHED • Add approximately 1/4gal. of water slowly from the air outlet and check drainage flow. • Check drainage flow during COOL running, explained under ‘‘12. TEST RUN’’. • Refer to the figure on the following after checking the draining of water, and mount the thermal insulation material for drainage (14) and thermal insulate the drain socket.
  • Page 17: Electric Wiring Work

    Power supply wiring terminal block Power supply single phase 208/230V Ground wire Ground terminal Control box cover Fig. 24 CAUTION Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sew- age might enter the indoor unit through the drain pipes and corrode the heat exchanger.
  • Page 18: Wiring Example And How To Set The Remote Controller

    8-2 Electrical characteristics Units Power supply Fan motor Model Volts Voltage range FCQ18PAVJU 0.056 FCQ24PAVJU 0.056 Max. 253 FCQ30PAVJU 208/230 0.056 Min. 187 FCQ36PAVJU 0.120 FCQ42PAVJU 0.120 MCA: Minimum Circuit Ampacity (A) MOP: Maximum Overcurrent Protective Device (A) kW: Fan Motor Rated Output (kW)
  • Page 19 [ PRECAUTIONS ] 1. Use round crimp-style terminals for connecting wires to the power supply terminal block. If unavailable, observe the following points when wiring. • Do not connect wires of different gauge to the same power supply terminal. (Looseness in the connection may cause overheating.) •...
  • Page 20 10. Use a 90° elbow type of conduit with dimensions Fig. 27-1 to prevent it from hitting the swing motor hous- ing of decoration panel. Conduit <1-3/8 Conduit mounting ≥3/8 plate (17) Conduit mounting Fig. 27-1 plate (18) Remote Transmission controller wiring wiring Conduit mounting...
  • Page 21 CAUTION • When clamping wiring, use the included clamping material to prevent outside pressure being exerted on the wiring connections and clamp firmly. When doing the wiring, make sure the wiring is neat and does not cause the control box cover to stick up, then close the cover firmly. •...
  • Page 22 1. When using 1 remote controller (Normal operation) Power supply 208/230V Outdoor unit 1 ~ 60Hz Control box IN/D OUT/D Indoor unit Remote Fig. 29 controller 2. When using 2 remote controllers Power supply 208/230V Outdoor unit 1~ 60Hz Control box IN/D OUT/D Indoor unit For use with...
  • Page 23 [ PRECAUTIONS ] 1. Do not ground the equipment on gas pipes, water pipes or lightning rods, or crossground with telephones. Improper grounding could result in electric shock. 9-3 Control by 2 remote controllers (controlling 1 indoor unit by 2 remote controllers) •...
  • Page 24: Installation Of The Decoration Panel

    9-4 Computerized control (forced off and on/off operation) (1) Wire specifications and how to perform wiring • Connect the input from outside to terminals T1 and T2 of the terminal block for remote controller. FORCED Input A Wire specification Sheathed vinyl cord or cable (2 wire) Gauge AWG18 - 16 Length...
  • Page 25: Field Setting

    11. FIELD SETTING CAUTION When performing field setting or test run without attaching the decoration panel, do not touch the drain pump. This may cause electric shock. • Check that the outdoor unit has been wired properly. Make sure the control box covers are closed on the indoor and outdoor units. Field setting must be made from the remote controller and in accordance with installation conditions.
  • Page 26: Test Run

    11-4 Setting of air filter sign • Remote controllers are equipped with liquid crystal display air filter signs to display the time to clean air filters. • Change the SECOND CODE NO. according to “Table 5” depending on the amount of dirt or dust in the room. (SECOND CODE NO.
  • Page 27 1645 Wallace Drive, Suite 110 Carrollton, TX 75006 USA info@daikinac.com www.daikinac.com 3P161684-6K EM11A061 (1110)