Field Setting - Daikin FCQ24TAVJU Installation Manual

Hide thumbs Also See for FCQ24TAVJU:
Table of Contents

Advertisement

10. FIELD SETTING

<<Refer to also the installation manual attached to the
outdoor unit.>>
CAUTION
Before carrying out field setting, check the items mentioned in
Clause 2: (1) Items to be checked after completion of work
on page 2. Check if all the installation and piping works for
the air conditioner are completed.
• Check if the control box covers of the air conditioner are
closed.
< FIELD SETTING >
<<After turn on the power supply, carry out field setting
from the remote controller according to the installation
state.>>
• Carry out setting at 3 places, MODE NO., FIRST CODE
NO. and SECOND CODE NO.
The settings shown by
when shipped from the factory.
• The method of setting procedure and operation is shown in
the installation manual attached to the remote controller.
• In case of remote control, for changeover of input to
FORCED OFF or to ON/OFF OPERATION.
[1] Enter into the field setting mode with the remote controller.
[2] Select MODE NO. 22.
[3] Set the FIRST CODE NO. to 1.
[4-1] For FORCE OFF, set the SECOND CODE NO. to 01.
[4-2] For ON/OFF OPERATION, set the SECOND CODE
NO. to 02.
(It is set to FORCE OFF when shipped from the factory.)
• Ask your customer to keep the manual attached to the
remote controller together with the operation manual.
• Do not carry out settings other than those shown in the
table.
10-1 SETTING CEILING HEIGHT
• Set the SECOND CODE NO. according to the ceiling height
as shown in the Table 4.
Table 4
Ceiling height [in. (m)]
Setting
30 · 36 · 42 · 48
18 · 24 type
type
≤ 8 to 3/4
≤ 10 to 1/2
Standard
(2.7 or less)
(3.2 or less)
8-3/4 to 10
10-1/2 to 12
High ceiling 1
(2.7 – 3.0)
(3.2 – 3.6)
10 to 11-1/2
12 to 13-3/4
High ceiling 2
(3.0 – 3.5)
(3.6 – 4.2)
10-2 SETTING AIR DISCHARGE DIRECTION
• Refer to the installation manual attached to the sealing ma-
terial of air discharge outlet sold separately and engineer-
ing data book, for ceiling height settings for four-direction
(part of corner closed off) and three-direction.
(The SECOND CODE NO. is factory set to 01 (all round
outlet) before shipping.)
10-3 SETTING WHEN AN OPTIONAL ACCESSORY
IS ATTACHED
• For setting when attaching an optional accessory, refer to
the installation manual attached to the optional accessory.
15
in the table indicate those
FIRST
SECOND
MODE
CODE
CODE
NO.
NO.
NO.
0
01
23
0
01
0
02
23
0
02
0
03
23
0
03
10-4 WHEN USING WIRELESS REMOTE CON-
TROLLER
• When using a wireless remote controller, it is necessary to
set the wireless remote controller address.
Refer to the installation manual attached to the wireless
remote controller.
10-5 SETTING FAN SPEED DURING THERMO-
STAT OFF
• Set the fan speed according to the using environment after
consultation with your customer.
• When the fan speed is changed, explain the set fan speed
to your customer.
Table 5
Setting
LL
Fan speed during
(Extra low)
cooling
thermostat OFF
Setting
LL
Fan speed during
(Extra low)
heating
thermostat OFF
Setting
10-6 SETTING FILTER SIGN
• A message to inform the air filter cleaning time will be indi-
cated on the remote controller.
• Set the SECOND CODE NO. shown in the Table 6 accord-
ing to the amount of dust or pollution in the room.
• Though the indoor unit is equipped with the long life filter, it
is necessary to periodically clean the filter to avoid clogging
of the filter. Please also explain the set time to the customer.
• The periodic filter-cleaning time can be shortened depend-
ing on the environment.
Table 6
Hours until
Contamination
indication
Approx.
Normal
2,500 hrs
More
Approx.
contaminated
1,250 hrs
With indication
No indication*
* Use No indication setting when cleaning indication is not neces-
sary such as the case of periodical clean ing being carried out.
MODE
FIRST
SECOND
NO.
CODE NO.
CODE NO.
01
22
6
02
01
22
3
02
SECOND
MODE
FIRST
CODE
NO.
CODE NO.
NO.
01
0
02
20
01
3
02
English