Daikin FCQ24TAVJU Installation Manual page 16

Hide thumbs Also See for FCQ24TAVJU:
Table of Contents

Advertisement

Wiring penetrating hole
Remote controller
wiring/transmission wiring
Sealing material
(Small) (13)
(accessory)
Putty or insulation
(field supply)
Fig. 24
<<Mending method of wiring penetrating hole>>
• After wiring connection is finished, to prevent the penetra-
tion of water, small animals and insects into the indoor unit
from the outside, mend the respective covers for wiring
penetrating hole for the power supply wiring/ground wiring
and the remote controller wiring/transmission wiring.
• Cut the sealing material (Small) (13) into two pieces and
wrap each wiring with each piece.
• Seal the clearance around the wirings with putty and insu-
lating material (field supply).
If insects and small animals get into the indoor unit, short
circuiting may occur inside the control box.
• Keep the distance of 1-15/16 in. (50 mm) or more between
low voltage wiring (remote controller wiring, transmission
wiring) and the high voltage wiring (power supply wiring,
ground wiring) at anywhere outside the indoor unit. If both
wirings are laid down together, they may be affected by
outside electrical noise and cause malfunction or failure.
8-5 WIRING EXAMPLE
COMPLETE SYSTEM EXAMPLE
Power supply
Outdoor unit
Main
switch
Remote controller
Fig. 25
13
Power supply wire
Transmission wire
Disconnect switch
Fuse/Breaker
Indoor unit
1.When using 1 remote controller (Normal operation)
Power Supply
208/230V
1~ 60Hz
L
L
1
2
Indoor unit
Fig. 26
2. When using 2 remote controllers
Power Supply
208/230V
1~ 60Hz
L
L
1
2
Indoor unit
Fig. 27
[ PRECAUTIONS ]
1. Do not ground the equipment on gas pipes, water pipes
or lightning rods, or crossground with telephones.
Improper grounding could result in electric shock.
2. The remote controller wiring (P ¹ and P ² ) and transmis-
sion wiring (F ¹ and F ² ) have no polarity.
Outdoor unit
Control box
IN/D OUT/D
F
1
F
2
F
1
F
2
L
L
P
P
F
F
T
T
1
2
1
2
1
2
1
2
P
P
1
2
Remote
controller
Outdoor unit
Control box
IN/D OUT/D
F
F
F
F
1
2
1
2
L
L
P
P
F
F
T
T
1
2
1
2
1
2
1
2
P
P
P
P
1
2
1
2
For use with
2 remote
controllers
English

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fcq18tavjuFcq30tavjuFcq36tavjuFcq42tavjuFcq48tavju

Table of Contents