11. TEST OPERATION

• The operation lamp of the remote controller will flash when
a malfunction occurs. Check the malfunction code on the
display to identify the point of trouble. An explanation of
malfunction codes and the corresponding trouble is pro-
vided in "Service precautions" of the outdoor unit.
If the display shows any of the following, there is a possibil-
ity that the wiring was done incorrectly or that the power is
not on, so check again.
Remote controller
display
" A8 "
Error in power supply voltage to indoor unit.
Test operation of outdoor unit has not been
" U3 "
finished.
There is a short circuit at the FORCED OFF
"
"
terminals (T ¹ , T ² )
The power on the outdoor unit is off.
The outdoor unit has not been wired for
" U4 "
power supply.
" UH "
Incorrect wiring for the transmission wiring
and / or FORCED OFF wiring.
The power on the indoor unit is off.
The indoor unit has not been wired for
power supply.
None
Incorrect wiring for the remote controller
wiring, the transmission wiring and / or the
FORCED OFF wiring.
CAUTION
After the test operation is completed, check the items
mentioned in 2. BEFORE INSTALLATION (2) Items to
be checked at time of delivery on page 2.
If the interior finish work is not completed when the test
operation is finished, for protection of the air conditioner,
ask the customer not to operate the air conditioner until
the interior finish work is completed.
If the air conditioner is operated, the inside of the indoor
unit may be polluted by substances generated from the
coating and adhesives used for the interior finish work
and cause water splash and leakage.
To the operator carrying out test operation
After the test operation is completed, before deliver-
ing the air conditioner to the customer, confirm that the
control box cover, the air filter and suction grille are
attached.
In addition, explain the power supply status (power sup-
ply ON/OFF) to the customer.