Configuring the Control Valve for No Hard Water Bypass Operation:
Select NO HARD BYPASS ENABLED for control operation. For no hard water bypass operation the three
wire connector is not used. Selection requires that a connection to MAV or a Clack No Hard Water Bypass
Valve is made to the two pin connector labeled MAV DRIVE located on the printed circuit board. If using a
MAV, the A port of the MAV must be plugged and the valve outlet connected to the B port. When set to No
Hard Water Bypass Enabled the MAV will be driven closed before the first regeneration cycle that is not
FILL or SOFTENING or FILTERING, and be driven open after the last regeneration cycle that is not FILL.
NOTE: If the control valve enters into an error state during regeneration mode, the no hard water bypass
valve will remain in its current state until the error is corrected and reset.
Configuring the Control Valve for Separate Source Operation:
Select Separate Source Enabled for control operation. For separate source operation, the three wire
connector is not used. Selection requires that a connection to a Clack Motorized Alternator Valve (MAV) is
made to the two pin connector labeled MAV DRIVE located on the printed circuit board. The C port of the
MAV must be connected to the valve inlet and the A port connected to the separate source used during
regeneration. The B port must be connected to the feed water supply.
When set to Separate Source Enabled the MAV will be driven closed before the first regeneration cycle,
and be driven open after the last regeneration cycle.
NOTE: If the control valve enters into an error state during regeneration mode, the MAV will remain in its
current state until the error is corrected and reset.
Configuring the Control Valve for Reclamation Mode:
Select Reclaim Enabled for control operation. The Alternating MAV transitions to Bypass at a set time after the start of regeneration. The
start of regeneration is defined as the first cycle that is not FILL, SOFTENING or FILTERING. The Alternating MAV will transition back to
Service after the completion of the preset duration time.
Configuring the Control Valve to operate with Clack System Controller:
Select System Controller Enabled to link the Control Valve to the Clack System Controller. For
communication between the Control Valve and the System Controller a three wire communication cable is
required.
Press NEXT to go to Step 4CS. Press REGEN to return to previous step.