To reset diagnostic data push "Next" and  button until TYPE appears in window, then press " & " button simultaneously for 3 seconds.
STEP 1D
[!J
EJEJEJ [!7
STEP 2D
DAYS SINCE REGEN
2
DAY
[!J
EJEJEJ [!7
STEP 3D
SINCE LAST REGEN
342
GAL
[!J
EJEJEJ [!7
STEP 4D
RESERVE HISTORY
0 160
DAY
GAL
[!J
EJEJEJ [!7
STEP 5D
USAGE HISTORY
108
1
DAY
GAL
[!J
EJEJEJ [!7
STEP 6D
MAX FLOW
6
12.7
DAY
GAL
[!J
EJEJEJ [!7
STEP 7D
ALT + FIRST
TTT
CCC
CYC
VVV
[!J
EJEJEJ [!7
RETURN TO NORMAL MODE
15

DIAGNOSTICS

STEP 1D – Press  or  simultaneously for three seconds. If screen in step 2D does not appear in 5
seconds the lock on the valve is activated.
STEP 2D – Days, since last regeneration: This display shows the days since the last regeneration
occurred. Press the NEXT button to go to Step 3D. Press REGEN to exit Diagnostics.
STEP 3D – Volume, since last regeneration: This display shows gallons of water that has been
treated since the last regeneration. This display will equal zero if a water meter is not installed. Press
the NEXT button to go to Step 4D. Press REGEN to return to previous step.
STEP 4D – Volume of reserve capacity used for last 7 days: If the unit is set up as a softener, a
meter is installed and Set Volume Capacity is set to "Auto", this display shows 0 day (for today) and
the reserve capacity. Pressing the  button will show day 1 (which would be yesterday) and displays
the reserve capacity. Pressing the  button again will show day 2 (the day before yesterday) and
the reserve capacity. Keep pressing the  button to show the capacity for days 3, 4, 5 and 6. The 
button can be pressed to move backwards in the day series. Press NEXT button at any time to go to
Step 5D. Press REGEN to return to previous step.
STEP 5D – Volume of water used, 63-day usage history: This display shows day 0 (for today) and
1 (for yesterday) will show day 2 (which would be the day before yesterday) and flashes the volume of
water treated on that day. Continue to press the  button to show the volume of water treated for the
last 63 days. If a regeneration occurred on the day the "letter R" will also be displayed. This display
will show dashes if a water meter is not installed. Press the NEXT button at any time to go to Step 6
D. Press REGEN to return to the previous step.
STEP 6D – Flow rate, maximum of each of last seven days: The maximum flow rate in gallons per
minute that occurred in each of the last seven days will be displayed. Press  arrow to display maxi-
mum flow rate today = 0, yesterday = 1. This display will equal zero if a water meter is not installed.
Press the NEXT button to exit Diagnostics. Press REGEN to return to the previous step.
STEP 7D – MAV Drive History – Not displayed if MAV set to off.
• First - Average of 1st three drive times of MAV in that direction
• Last - Last drive time measured for that MAV in that direction
• Ave - Average drive time measured for MAV in that direction
• TTT - Drive time (1424 = 14.24 seconds)
• CCC - Total number of cycles for that MAV
• VVV - Relative drive voltage
MAV drives piston "in" is designated by (-) sign.
MAV drives piston "out" is designated by (+) sign.
Any time MAV is rebuilt or replaced, reset diagnostics to reflect new drive characteristics.