Hellenbrand H200M HE-16 Owner's Manual page 13

Table of Contents

Advertisement

"TIME"
STEP 12S
RELAY 1
SET
[!J
EJEJEJ [!7
SET POINT - MINUTES
10
SET
[!J
EJEJEJ [!7
DURATION
3:00
SET
[!J
EJEJEJ [!7
"GALLONS"
RELAY 1
SET
[!J
EJEJEJ [!7
RELAY 1 SET POINT
1
SET
GAL
[!J
EJEJEJ [!7
RELAY 1 DURATION
0:01
MIN
SET
[!J
EJEJEJ [!7
"REGEN GALLONS"
RELAY 1
SET
[!J
EJEJEJ [!7
13
STEP 12S – Set Relay to activate by Time, Gallons, Regen Gallons, Off or Service Alarm by using 
or  buttons. A relay can be used to operate a chemical feed pump or solenoid. The choices are:
• Relay Triggered on Time - Relay activates after set number of minutes after start of regeneration. Start of
regeneration is defined by first backwash cycle, dn brine or up brine, whichever is first.
Relay deactivates after set time. (Range: 0 – 500 minutes)
• Relay Triggered on Gallons - Relay activates every set number of gallons while in service and deacti-
vates after set time. (Range: 0.1 – 20,000 gallons)
• Relay Triggered on Regen Gallons - Relay activates after set number of gallons in service or gallons
used during regeneration and de-activates after set time or when meter stops registering flow, which-
ever comes first. (Range: 0.1 –20,000 gallons)
• Service Alarm - Relay activates on service alarm setting: gallons, time or both.
• Relay Triggered for Lock Out - Relay activates after set number of minutes into regeneration. A zero
or positive start time references the first backwash or brine cycle as start. "Regen" can be selected
for time setting to activate relay for entire regeneration cycle; 2 minutes before and 1 minute after.
"Regen" can be selected as lockout setpoint by pressing down arrow through all negative numbers.
(Range -20 – 500 minutes)
• Factory setting = OFF. Press NEXT to go to next step or other selection for relay settings.
If off was selected in previous step, this screen does not appear.
If Time chosen to Activate Relay, use up and down arrows to set # of minutes AFTER START OF
REGEN to activate relay. Start of regeneration is defined as first Backwash or Regenerant Draw
mode. Press NEXT to go to next step..
Use Up and Down arrows to set duration of relay activation in minutes.
Time Range = Negative 20 minutes to a positive 500 minutes. Press NEXT to go to next step.
Press REGEN to return to previous step.
Gallons chosen to activate relay. If Off or Time was selected in previous steps, this screen does not ap-
pear. Press NEXT to set # of gallons per relay activation.
Use up and down arrows to set # of gallons per relay activation.
Range = 0.1–20,000 gallons. Press NEXT to set duration of relay activation.
Use up and down arrows to set duration of relay activation in minutes.
Range = 1 second - 500 minutes (0:01–500:00). Press NEXT to go to next step.
Press REGEN to return to previous step.
If REGEN gallons chosen to activate relay. Relay activates after set number of gallons have been
used in service or during regeneration and then deactivates after set period of time or after flow stops,
whichever comes first. Range = 0.1–20,000 gallons. Press NEXT to go to next step.