Master Code Reset; Control Panel Enrollment To; Control Panel; Setting - jablotron Oasis JA-80 Installation Manual

Hide thumbs Also See for Oasis JA-80:
Table of Contents

Advertisement

3. In the sub control panel, enter enrollment mode by keying in
"1" in Service Mode and select the desired address.
4. In the master control panel enter 290. This way the control
panel will enroll to the sub control panel to the desired
address as a remote control.
5. Switch both control panels to maintenance mode and check
that all-section setting of the master control panel also sets
the sub control panel and unsetting the master control panel
unsets the sub control panel too. Expect approximately 2
seconds of delay between control panels.
Notes for operating the sub control panel:
• The sub control panel can still be operated independently via its
keyfob or keypad e.g. it can be set while the master control panel is
unset. If the master control panel changes its status later on, it will
then control the sub control panel to achieve synchronisation.
• To disable the master control panel's ability to control the sub control
panel, enter the sub control panel's enrollment mode, select the
address where the master control panel is enrolled and erase the
master control panel from this address by pressing and holding key 2.

12.11. Master code reset

If the master code has been forgotten or a card lost, it is
possible to use the following sequence to reset the master code
to the factory-default 1234:
291
Note: Resetting the master code has no effect on other codes and
cards. Resets are recorded in the control panel memory and sent to the
ARC if used (Alarm Receiving Centre, previously called a central
monitoring station).
12.12. Control panel enrollment to UC or AC modules
or to a sub control panel
Keying in
sends an enrollment signal to enroll the control
299
panel to UC-82 or AC-82 receiving modules (see 11.6). This
sequence can also be used to enroll a sub control panel to a
master control panel (see 12.10).
12.13. Setting (Arming) without an access code
"Hot" setting keys (short-cut keys for setting) A, B, ABC or
entering "∗ number" can be enabled for use without a valid access
code or card. If disabled, then hot key use or entering "∗ number"
has to be followed by a valid access code or card to have any
effect:
Function/sequence
All-section setting
Setting of A
Setting of AB (or B)
Event memory recall
• If you remotely operate the system by mobile phone, you can
press ∗1 for the ABC key, ∗2 for key A, and ∗3 for key B.
• Controlling the PG outputs by keying in ∗8 or ∗9 or pressing
and
is unaffected by these settings. These keys can
however be disabled by a special sequence (see 12.27).
Factory default setting: Setting (arming) without an access
code enabled.

12.14. Triggered-detector indication

Pressing the ? key checks if any detectors are permanently
triggered, e.g. if any doors or windows are open. The following
sequence enables the display of text concerning active
detectors.
3 1 1 indication enabled
3 1 0 indication disabled
Factory default setting: indication enabled
Installation manual: Oasis security system JA-80K
301
300
ABC key
Code/card
A key
A key, code/card
B key
B key, code/card
∗4
∗4 code/card

12.15. Confirmation of intruder alarms

To reduce the risk of false alarms and to comply with British
standard
BSI
DD243,
confirmation logic to be enabled as follows:
3 2 1 confirmation logic enabled
3 2 0 confirmation logic disabled
Confirmation logic:
• If the system is set (armed) and any intruder detector gets
triggered, i.e. a detector with an instant, delayed, or next-
delayed reaction, an alarm will not be caused but the control
panel will record a so-called unconfirmed alarm.
• If any other intruder detector is triggered in a set section within
40 minutes of the above event, an intruder alarm will be
triggered. If no other detector is triggered during this period,
the control panel will stop waiting for confirmation.
• The alarm must be confirmed by another detector than the
first one, and if the second one is a motion detector its
detection area must not cover the same area as the first
detector to be triggered. This must be ensured by the proper
location of detectors.
• An unconfirmed alarm is recorded in control panel memory but
can also be sent to the ARC, or to the user by SMS report.
• If the first triggered detector has a delayed reaction, it will start
a so-called unconfirmed entrance delay. This delay is
indicated the same way as an ordinary entrance delay, but if
no other delayed detector is triggered during this delay, there
will be no alarm if the unconfirmed entrance delay is
exceeded, with another unconfirmed alarm being recorded in
the control panel memory. If there is any other delayed or
next-delayed detector triggered during the entrance delay
period, it will confirm the entrance delay, and if this delay is
exceeded (due to no unsetting being done) it will trigger an
intruder alarm at the end of the delay.
• If the unconfirmed entrance delay is confirmed by an instant
detector it will trigger an internal warning alarm immediately
(e.g. an internal siren) and if the entrance delay times out then
an external alarm will be triggered.
• An unconfirmed alarm can be confirmed by any other intruder
detectors in the system as long as the detectors are assigned
to a set (armed) section.
• The confirmation of intruder alarms has no effect on fire,
panic, 24-hour, tamper, or technical alarms. These alarms are
triggered immediately without confirmation.
Note: When the first detector is triggered it begins a process
which waits 40 minutes for any possible confirmation of the
alarm (unconfirmed alarm status) during which the system works
exactly the same way as if the confirmation function had not
been enabled.
If intruder alarm confirmation is enabled, it is
Warning:
necessary to install enough detectors in the building to detect an
intruder even if he/she is only moving in one particular place.
Factory default setting: confirmation disabled

12.16. Exit delay beeps

The exit delay can be indicated by beeps from the keypad and
internal siren. The beeps get faster in the last 5 seconds.
3 3 1 Beeps enabled
3 3 0 Beeps disabled
Factory default setting: Beeps enabled.
- 12 -
the
control
panel
allows
alarm
MKE51801