Installing The Server In A Cabinet - EMC SVR-I2U-R2312 Installation And Maintenance Manual

Advertisement

Operating limits
Shipping and storage requirements

Installing the server in a cabinet

Rating label on the chassis. For additional information, refer to the preparation/planning
guides for your specific site and cabinet.
The ambient temperature specification is measured at the front bezel inlet. The site must
have air conditioning of the correct size and placement to maintain the specified ambient
temperature range and offset the heat dissipation listed in the table that follows.
Table 3 Operating limits
Requirement
-
Ambient temperature
Temperature gradient
Relative humidity extremes
Recommended operating relative
humidity
Elevation
* For altitudes above 2,950 feet, the maximum operating temperature is de-rated 1°F/550 ft.
Table 4 Shipping and storage requirements
Requirement
-
Ambient temperature
Temperature gradient
Relative humidity
Elevation
To install the server in a cabinet you must perform the tasks below in the order listed.
This section describes how to perform each task.
1. Review the warnings and recommendations section.
2. Verify the contents of the mounting kit.
3. Adjust the rail assemblies for the cabinet channel holes.
4. Remove the inner rails from the rail assemblies.
5. Attach the inner rails to the server.
6. Install the slide rails in the cabinet.
7. Install the server on the slide rails in the cabinet.
8. Connect cables to the server.
9. Install the bezel on the server.
Description
-
10°C to 35°C (50°F to 95°F)
10°C/hr (18°F/hr)
20% to 80% noncondensing
40% to 55% noncondensing
-50 to 10,000 ft (-16 to 3,048 m)*
Description
-
-40°C to 65°C (-40°F to 149°F)
25°C/hr (45°F/hr)
10% to 90% noncondensing
-50 to 35,000 ft (-16 to 10,600 m)
Operating limits
3