14.3.9 Symptom: The pressure at the tapping point is temporarily unusually high
14.3.10 Symptom: Decoration panels are pushed away due to a swollen tank
14.3.11 Symptom: Tank disinfection function is NOT completed correctly (AH-error)
ERGA04~08EA + EHVZ04+08S18+23EA
Daikin Altherma 3 R F
4P629093-1A – 2021.11
Possible causes
The backup heater equilibrium
temperature has not been configured
correctly
There is air in the system.
Too much heat pump capacity is used
for heating domestic hot water
Possible causes
Failing or blocked pressure relief valve.
Possible causes
Failing or blocked pressure relief valve.
Possible causes
The disinfection function was
interrupted by domestic hot water
tapping
14
Troubleshooting
|
Corrective action
Increase the equilibrium temperature to
activate the backup heater operation at
a higher outdoor temperature.
Go to: [9.3.7]: Installer settings
> Backup heater > Equilibrium
temperature [5‑01]
Purge air manually or automatically. See
the air purge function in the chapter
4
"11 Commissioning" [
211].
Check if the Space heating
priority settings have been
configured appropriately:
▪
Make sure that the Space heating
priority has been enabled.
Go
to
[9.6.1]:
settings > Balancing > Space
heating priority [5‑02]
▪
Increase the "space heating priority
temperature" to activate backup
heater operation at a higher outdoor
temperature.
Go
to
[9.6.3]:
settings
>
Balancing
Priority temperature [5‑03]
Corrective action
▪
Flush and clean the complete tank
including the piping between pressure
relief valve and the cold water inlet.
▪
Replace the pressure relief valve.
Corrective action
Contact your local dealer.
Corrective action
Program the start-up of the disinfection
function when the coming 4 hours NO
domestic hot water tapping is expected.
Installer
Installer
>
Installer reference guide
235