Universal controller TCI-W13-U-H/TCI-W23-U-H
Control parameters (password 241)
Warning! Only experts should change these settings! The parameters are grouped according to
control modules. After completing the logging in, a control module must be selected before
accessing the parameters.
Module
Description
UI
Input configuration: 1T, 1H, 1U, 2T
LP
Control loops Lp1, Lp2
AO
Analog output configuration, AO1, AO2
DO
Binary output configuration, do1
FU
Special functions
Internal input configuration (TI1)
Parameter Description
1t 00
Enable internal sensor
1t 01
Display minimum value
1t 02
Display maximum value
1t 03
Sensor sampling rate(control speed decrease as rate
increases)
1t 04
Sensor calibration
1t 05
Alarm 1 low limit (1T), alarm 3 low limit (1H)
1t 06
Alarm 1/3 low limit values
1t 07
Alarm 2high limit (1T), alarm 4high limit (1H)
1t 08
Alarm 2/4 high limit values
1t 09
Hysteresis alarm 1, 2, 3, 4
1t 10
Calculate a range of inputs (0= not active):
1= average, 2= minimum, 3= maximum
Internal input configuration (HI1)
Parameter Description
1H00
Enable internal sensor
1H01
Display minimum value
1H02
Display maximum value
1H03
Sensor sampling rate(control speed decrease as rate
increases)
1H04
Sensor calibration
1H05
Alarm 1 low limit (1T), alarm 3 low limit (1H)
1H06
Alarm 1/3 low limit values
1H07
Alarm 2high limit (1T), alarm 4high limit (1H)
1H08
Alarm 2/4 high limit values
1H09
Hysteresis alarm 1, 2, 3, 4
1H10
Calculate a range of inputs (0= not active):
1= average, 2= minimum, 3= maximum
External input configuration (UI1, TI2)
Parameter
Description
1u 00
2t 00
Signal type (0= not active):
1= 0...10V or 0...20mA or open contact, 2= 2...10 V or
4...20 mA, 3= NTC temperature sensor
1u 01
2t 01
Display minimum value
1u 02
2t 02
Display maximum value
Analog input display range:
1u 03
2t 03
0= x0.1, 1= x1, 2= x10, 3 = x100
1u 04
2t 04
Analog input unit of measure:
0= no unit, 1= %, 2= °C /°F, 3= Pa
1u 05
2t 05
Sensor sampling rate
(control speed decrease as rate increases)
1u 06
2t 06
Sensor calibration
1u 07
2t 07
Alarm 5 low limit (1u), alarm 7 low limit (2t)
1u 08
2t 08
Alarm 5 low limit value (1u), alarm 7 low limit value (2t)
1u 09
2t 09
Alarm 6 high limit (1u), alarm 8 high limit (2t)
1u 10
2t 10
Alarm 6 high limit value 1u), alarm 8 high limit value (2t)
1u 11
2t 11
Hysteresis alarm 5 and 6 (1u), alarms 7 and 8 (2t)
1u 12
2t 12
Calculate a range of inputs (0=not active):
1= average, 2= minimum, 3= maximum, 4= differential
Doc: 70-00-0384A V1.0 20160523
LP: Control parameters (1L)
Parameter Description
Select loop control input (0= loop disabled):
1L 00
1= 1T, 2= 1H, 3= 1U, 4= 2T
1L 01
Minimum set point limit heating
1L 02
Maximum set point limit heating
1L 03
Minimum set point limit cooling
1L 04
Maximum set point limit cooling
Enable set point compensation (0= disabled)
1L 05
1= winter compensation, 2= summer compensation, 3= winter
and summer
Loop input special (0= normal):
1= combine loop 1 and loop 2
Range
Standard
2= cascade with reverse sequence of primary loop
1L 06
ON, OFF
OFF
3= cascade with direct sequence primary loop
4= cascade with both reverse and direct sequence of
-50...205
0
primary loop
-50...205
100
Economy mode set point shift: (Function depends on 1L25)
The comfort (occupied) set point is shifted by the value set with
0...100
10
1L 07
parameter. Reduces the heating set point and increases the
-10.0...10.0
0
cooling set point.
Dead zone between heating and cooling set points
OFF, ON
OFF
The dead zone span lies between the heating and the cooling set
-50...205 °C
5°C (41°F)
1L 08
point. The output is off while the measured value is within the
OFF, ON
OFF
dead zone span. A negative dead zone is not possible.
-50...205 °C
50°C (122°F)
1L 09
Offset for heating PI sequence
0...100 °C
5°C (10°F)
1L 10
Offset for cooling PI sequence
0...3
0
1L 11
P-band heating
1L 12
P-band cooling
Integral gain heating (0.1 steps)
Range
Standard
1L 13
low= slow reaction, high= fast reaction
ON, OFF
ON
1L 14
Integral gain cooling (0.1 steps)
-50...205
0
Measuring interval integral (seconds)
-50...205
100
1L 15
low= fast reaction, high value= slow reaction
0...100
10
Action of stages:
0= cumulative: stage 1 stays on when 2 on comes on
-10.0...10.0
0
1L 16
1= single: stage 1 turns off when 2 on comes on
OFF, ON
OFF
2= digital: stage 1 only, stage 2 only, then stage 1 plus 2
0...100%
5%
1L 17
Offset for heating/reverse binary sequences
OFF, ON
OFF
1L 18
Offset for cooling/direct binary sequences
0...100%
95%
1L 19
Switching span heating
0...100%
5%
1L 20
Switching span cooling
0...3
0
1L 21
Switching hysteresis
1L 22
Switching delay
Activation of reverse/direct (heat/cool) sequence
Range
Standard
1L 23
OFF= activates based on demand
ON = follows heat/cool state of controller
0...3
0
1L 24
Delay for heat /cool changeover when L23=OFF
-50...205
0
Fixed set point in standby mode
1L 25
OFF = Standby set point shift applies
-50...205
100
ON = In standby mode use minimum set point limit as set point in
0...2
1
heating mode or maximum set point limit in cooling mode
Set point compensation range, the maximum range the set point
1L 26
0...3
2
is shifted.
0 = Temperature setback: the set point is shifted towards set point
0...100
10
limit
Range dep
0
OFF, ON
OFF
-50...205 °C
5°C (41°F)
OFF, ON
OFF
-50...205 °C
50°C (122°F)
0...100 °C
5°C (10°F)
0...4
0
Universal controller TCI-W13-U-H/TCI-W23-U-H
Range
Standard
0...4
2
per input
10%
per input
90%
per input
10%
per input
90%
0...3
0
0...4
0
per input
10%
per input
5%
per input
0
per input
0
per input
10%
per input
10%
0...25.5
0.0
0...25.5
0.0
0...255
1
0...2
0
per input
0%
per input
0%
per input
10%
per input
10%
per input
5%
0...255s
30s
ON/OFF
OFF
0...255 min
5 min
ON, OFF
OFF
Acc input
0.0 °C
© Vector Controls GmbH, Switzerland
Universal controller TCI-W13-U-H/TCI-W23-U-H
LP: Control parameters (2L)
Parameter Description
Select loop control input (0= loop disabled):
2L 00
1= 1T, 2= 1H, 3= 1U, 4= 2T
2L 01
Minimum set point limit heating
2L 02
Maximum set point limit heating
2L 03
Minimum set point limit cooling
2L 04
Maximum set point limit cooling
Enable set point compensation (0= disabled)
2L 05
1= winter compensation, 2= summer compensation, 3= winter
and summer
Loop input special (0= normal):
1= combine loop 1 and loop 2
2= cascade with reverse sequence of primary loop
2L 06
3= cascade with direct sequence primary loop
4= cascade with both reverse and direct sequence of
primary loop
Economy mode set point shift: (Function depends on 2L25)
The comfort (occupied) set point is shifted by the value set with
2L 07
parameter. Reduces the heating set point and increases the
cooling set point.
Dead zone between heating and cooling set points
The dead zone span lies between the heating and the cooling set
2L 08
point. The output is off while the measured value is within the
dead zone span. A negative dead zone is not possible.
2L 09
Offset for heating PI sequence
2L 10
Offset for cooling PI sequence
2L 11
P-band heating
2L 12
P-band cooling
Integral gain heating (0.1 steps)
2L 13
low= slow reaction, high= fast reaction
2L 14
Integral gain cooling (0.1 steps)
Measuring interval integral (seconds)
2L 15
low= fast reaction, high value= slow reaction
Action of stages:
0= cumulative: stage 1 stays on when 2 on comes on
2L 16
1= single: stage 1 turns off when 2 on comes on
2= digital: stage 1 only, stage 2 only, then stage 1 plus 2
2L 17
Offset for heating/reverse binary sequences
2L 18
Offset for cooling/direct binary sequences
2L 19
Switching span heating
2L 20
Switching span cooling
2L 21
Switching hysteresis
2L 22
Switching delay
Activation of reverse/direct (heat/cool) sequence
2L 23
OFF= activates based on demand
ON = follows heat/cool state of controller
2L 24
Delay for heat /cool changeover when L23=OFF
Fixed set point in standby mode
2L 25
OFF = Standby set point shift applies
ON = In standby mode use minimum set point limit as set point
in heating mode or maximum set point limit in cooling mode
Set point compensation range, the maximum range the set point
2L 26
is shifted.
0 = Temperature setback: the set point is shifted towards
set point limit
Range
Standard
0...4
0
per input
10°C(50°F)
per input
28°C(82°F)
per input
18°C(64°F)
per input
34°C(93°F)
0...3
0
0...4
0
per input
5.0°C(10°F)
per input
1.0°C (2°F)
per input
0
per input
0
per input
2.0°C(4.0°F)
per input
2.0°C (4.0°F)
0...25.5
0.0
0...25.5
0.0
0...255
1
0...2
0
per input
0.0°C (0.0°F)
per input
0.0°C (0.0°F)
per input
1.0°C (2.0°F)
per input
1.0°C (2.0°F)
per input
0.5°C (1.0°F)
0...255
10
ON, OFF
OFF
0...255 min
5 min
ON, OFF
OFF
Acc input
0.0°C
Subject to alterations