Download Print this page

Delta DTB4824 Instruction Sheet page 2

Dtb series temperature controller
Hide thumbs Also See for DTB4824:

Advertisement

Set Value
Alarm Type
Reverse deviation upper- and lower-limit:
4
This alarm output operates when PV value is in the range of the setting value SV+(AL-H)
and the setting value SV-(AL-L).
Absolute value upper- and lower-limit:
5
This alarm output operates when PV value is higher than the setting value AL-H or lower
than the setting value AL-L.
Absolute value upper-limit:
6
This alarm output operates when PV value is higher than the setting value AL-H.
Absolute value lower-limit:
7
This alarm output operates when PV value is lower than the setting value AL-L.
Deviation upper- and lower-limit with standby sequence:
8
This alarm output operates when PV value reaches set point (SV value) and the value is
higher than the setting value SV+(AL-H) or lower than the setting value SV-(AL-L).
Deviation upper-limit with standby sequence:
9
This alarm output operates when PV value reaches set point (SV value) and the reached
value is higher than the setting value SV+(AL-H).
Deviation lower-limit with standby sequence:
10
This alarm output operates when PV value reaches the set point (SV value) and the
reached value is lower than the setting value SV-(AL-L).
Hysteresis upper-limit alarm output:
11
This alarm output operates if PV value is higher than the setting value SV+(AL-H). This
alarm output is OFF when PV value is lower than the setting value SV+(AL-L).
Hysteresis lower-limit alarm output:
12
This alarm output operates if PV value is lower than the setting value SV-(AL-H). This
alarm output is OFF when PV value is higher than the setting value SV-(AL-L).
CT alarm output:
This alarm operates when the current measured by transformer (CT) is lower than AL-L or
13
higher than AL-H (This alarm output is available only for the controller with current
transformer).
14
When program control is end status, alarm output is ON.
15
When RAMP UP status happens to PID program control, alarm output is ON.
16
When RAMP DOWN status happens to PID program control, alarm output is ON.
17
When SOAK status happens to PID program control, alarm output is ON.
18
When RUN status happens to PID program control, alarm output is ON.
Note: AL-H and AL-L include AL1H, AL2H, AL3H and AL1L, AL2L, AL3L
Current Transformer (CT) Function
The Current Transformer (CT) function is used with the alarm output. When using a current transformer (CT) with the
controller, change the corresponding alarm output mode to mode 13 (alarm output set value is 13), then turn to operation
mode and set the current lower-limit and current upper-limit. You can set current alarm range between 0.5A ~ 30A, display
resolution is 0.1A and measure accuracy is +/- 0.5A.
EVENT Inputs Function
There are two optional event inputs (contact inputs) supported (EVENT1and EVENT2) in DTB series.
EVENT1 : RUN/STOP operation can be executed by RUN/STOP parameters (Operation Mode) or via the communication.
User also can control RUN/STOP operation by EVENT 1 in DTB series. The control output is ON if the circuit of EVENT 1
is open when the controller is operating. Otherwise, the controller will stop output if the circuit of EVENT 1 is short or when
the system parameter of the controller is set to STOP mode.
EVENT2 : DTB series allows user can switch two temperature setting value by changing the status (open/short) of EVENT
2. Each temperature setting value has independent control parameters.
PID Program Control (Ramp/Soak Program Control)
Description of Function and Parameters Setting:
PID program control by 8 patterns (Pattern No. 0~7) is supported in DTB series. Each pattern contains 8 steps (step No. 0
~ 7), one Link Pattern parameter, one Cycle parameter and one Actual Step parameter
Start Pattern :
is in operation mode and it is used to set the Start Pattern of PID program control (This parameter
appear in
mode only).
Steps : Include set point X and execution time T, these two parameters setting. The set point (SV) should reach
temperature X after the period of execution time T. If the set point is the same as the result of the previous setting, then it is
called Soak program control. If not, then it is called Ramp program control. Therefore, PID program control is also called
Ramp/Soak program control.
The default of step No. 0 in this controller is Soak program control. The controller will control the temperature (PV) to
reach the set point X and then keep the temperature at set point X. The period of execution time is time T which provided
by step No. 0.
Link Pattern Parameter : For example, when set
to 2, it indicates that pattern No. 2 will execute next after the
execution of pattern No. 0. If set to
, it indicates the program will stop after executing the current pattern and the
temperature will keep at the set point of the last step.
Cycle Parameter : Additional execution cycle number. For example, when set
should execute twice in addition. Include origin one time execution, total execute three times.
Actual Step Parameter : Execution step number per pattern (can set to 0 ~ 7). For example, when set
indicates that pattern No 7 will not execute other steps than step 0 to step2.
Execution : When
is set to
, the program will start to execute in order from the step 0 of start pattern.
When
is set to
, the program will stop and the control output is disabled.
When
is set to
, the program will stop and the temperature at that time will be controlled at the set point
before program stop. Select
again, then the program will restart and execute from step 0 of start pattern.
When
is set to
, the program will hold and the temperature at that time will be controlled at the set point
before program hold. Select
again, then the program will follow the step before hold and start to execute through
the rest of the time.
Display : During PID program control, the SV default display is P-XX, P indicates the current execution pattern and XX
indicates the current execution step. Press
to change the display item.
After select
, press
key, and then the temperature set point of the current execution step will display on SV
display.
After select
, press
key, and then the residual time of the current execution step will display on SV display.
PID Control
One group can be selected from any one of 4 groups PID parameters (P, I, D, IOF) for PID control. After AT, PID value and
temperature setting will be stored in the selected one group.
~
: PIDn, n = 0 ~ 4 from which 0 ~ 3 correspond to each PID parameter.
Program will automatically select a most useful PID parameter based on current temperature setting. Displayed SV values
correspond to
~
~
: Temperature setting corresponded to the selected PID parameter via user-defined or AT.
Valve Control:
When use valve control as output control, there are 2 Relay outputs for motor forward/reverse control, one (output 1) for
valve open the other (output 2) for valve close. The output volume is controlled by valve open/close and it can be set with
feedback function enabled or disabled. When feedback is disabled, output 1 will keep output while valve fully opens and
output 2 will keep output while valve fully closes. But if feedback is enabled, please follow the parameter setting for valve
control as follows:
: Time for valve from full close to full open.
Alarm Output Operation
: Dead Band setting of valve. The value of current valve output minus previous one must be greater than Dead Band
ON
value; otherwise, valve will remain OFF.
OFF
SV-(AL-L)
SV
SV+(AL-H)
: Signal feedback setting, ON for enabling feedback and OFF for disabling feedback.
ON
When
set to " 1", it means signal feedback function is activated and will come up selections as follows:
OFF
a.
: Upper/Lower limit of valve feedback by auto-tuning.
AL-L
AL-H
ON
b.
: D/A value when value fully opens. Set
OFF
AL-H
c.
: D/A value when value fully closes. Set
ON
OFF
Note: If feedback function setting is with problem, program will see the setting as feedback disabled.
AL-L
RS-485 Communication
ON
OFF
1. Supporting transmission speed: 2,400, 4,800, 9,600, 19,200, 38,400bps
SV-(AL-L)
SV+(AL-H)
SV
2. Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E, 2
ON
3. Communication protocol: Modbus (ASCII or RTU)
OFF
4. Function code: 03H to read the contents of register (Max. 8 words). 06H to write 1 (one) word into register. 02H to read
SV
SV+(AL-H)
the bits data (Max. 16 bits). 05H to write 1 (one) bit into register.
ON
5. Address and Content of Data Register:
OFF
SV
SV-(AL-L)
Address
Content
ON
OFF
AL-L AL-H
1000H
Process value (PV)
ON
OFF
AL-H AL-L
ON
1001H
Set point (SV)
OFF
AL-L
AL-H
SV
1002H
Upper-limit of temperature range
1003H
Lower-limit of temperature range
1004H
Input temperature sensor type
1005H
Control method
1006H
Heating/Cooling control selection
1007H
1st group of Heating/Cooling control cycle
1008H
2nd group of Heating/Cooling control cycle
1009H
PB Proportional band
100AH
Ti Integral time
100BH
Td Derivative time
100CH
Integration default
100DH
Proportional control offset error value, when Ti = 0
The setting of COEF when
100EH
control
are used
The setting of Dead band when
100FH
output control
are used
1010H
Hysteresis setting value of the 1st output group
1011H
Hysteresis setting value of the 2nd output group
1012H
Output value read and write of Output 1
1013H
Output value read and write of Output 2
1014H
Upper-limit regulation of analog linear output
1015H
Lower-limit regulation of analog linear output
1016H
Temperature regulation value
1017H
Analog decimal setting
1018H
Time for valve from full open to full close
1019H
Dead Band setting of valve
101AH
Upper-limit of feedback signal set by valve
101BH
Lower-limit of feedback signal set by valve
101CH
PID parameter selection
101DH
SV value corresponded to PID value
1020H
Alarm 1 type
1021H
Alarm 2 type
1022H
Alarm 3 type
1023H
System alarm setting
1024H
Upper-limit alarm 1
1025H
Lower-limit alarm 1
1026H
Upper-limit alarm 2
1027H
Lower-limit alarm 2
1028H
Upper-limit alarm 3
1029H
Lower-limit alarm 3
102AH
Read LED status
102BH
Read pushbutton status
102CH
Setting lock status
to 2, it indicates that pattern No. 4
102DH
CT read value
102FH
Software version
1030H
Start pattern number
to 2, it
1040H~
Actual step number setting inside the correspond
1047H
pattern
1050H~
Cycle number for repeating the execution of the
1057H
correspond pattern
1060H~
Link pattern number setting of the correspond
1067H
pattern
2000H~
Pattern 0~7 temperature set point setting
203FH
Pattern 0 temperature is set to 2000H ~ 2007H
2080H~
Pattern 0~7 execution time setting
20BFH
Pattern 0 time is set to 2080H~2087H
6. Address and Content of Bit Register: ( First bit of reading will put into LSB, Write data = FF00H for bit set, 0000H for bit
clear)
0810H
Communication write-in selection
0811H
Temperature unit display selection
0812H
Decimal point position selection
0813H
AT setting
0814H
Control RUN/STOP setting
0815H
STOP setting for PID program control
0816H
Temporarily STOP for PID program control
0817H
Valve feedback setting status
: n = 4, auto PID parameter.
0818H
Auto-tuning valve feedback status
7. Communication Transmission Format: Command Code:02:read N bits,05:write 1 bit,03:read N words,06:write 1 word.
Panel Cutout & Terminal Definitions
Panel Cutout (dimensions are in millimeter and inch)
DTB4824
must set to
for showing up this selection.
to be "1" for auto setting or "0" for manual setting.
to be "1" for auto setting or "0" for manual setting.
Explanation
Measuring unit is 0.1, updated one time in 0.4 second
The following reading value display indicates error occurs:
8002H : Initial process (Temperature value is not got yet)
8003H : Temperature sensor is not connected
8004H : Temperature sensor input error
8006H : Cannot get temperature value, ADC input error
8007H : Memory read/write error
o
o
Unit is 0.1,
C or
F
The data content should not be higher than the temperature range
The data content should not be lower than the temperature range
Please refer to the contents of the "Temperature Sensor Type and
Temperature Range" for detail
0: PID, 1: ON/OFF, 2: manual tuning, 3: PID grogram control
0: Heating, 1: Cooling, 2: Heating/Cooling, 3: Cooling/Heating
0 ~ 99, 0:0.5 sec
0 ~ 99, 0:0.5 sec
0.1 ~ 999.9
0 ~ 9,999
0 ~ 9,999
0 ~ 100%, unit is 0.1%
0 ~ 100%, unit is 0.1%
Dual Loop output
0.01 ~ 99.99
Dual Loop
-999 ~ 9,999
0 ~ 9,999
0 ~ 9,999
Unit is 0.1%, write operation is valid under manual tuning mode only.
Unit is 0.1%, write operation is valid under manual tuning mode only.
1 Unit = 2.8uA (Current Output) = 1.3mV (Linear Voltage Output)
1 Unit = 2.8uA (Current Output) = 1.3mV (Linear Voltage Output)
-999 ~ +999, unit: 0.1
0 ~ 3
0.1 ~ 999.9
0 ~ 100%; unit: 0.1%
0 ~ 1,024
0 ~ 1,024
0 ~ 4
Only valid within available range, unit: 0.1 scale
Please refer to the contents of the "Alarm Outputs" for detail
Please refer to the contents of the "Alarm Outputs" for detail
Please refer to the contents of the "Alarm Outputs" for detail
0 : None (default), 1~3 : Set Alarm 1 to Alarm 3
Please refer to the contents of the "Alarm Outputs" for detail
Please refer to the contents of the "Alarm Outputs" for detail
Please refer to the contents of the "Alarm Outputs" for detail
Please refer to the contents of the "Alarm Outputs" for detail
Please refer to the contents of the "Alarm Outputs" for detail
Please refer to the contents of the "Alarm Outputs" for detail
b0 : Alm3, b1: Alm2, b2: F, b3:
, b4: Alm1, b5: OUT2, b6: OUT1, b7: AT
b0 : Set, b1 : Select, b2 : Up, b3 : Down. 0 is to push
0 : Normal, 1 : All setting lock, 11 : Lock others than SV value
Unit: 0.1A
V1.00 indicates 0x100
0 ~ 7
0 ~ 7 = N, indicate that this pattern is executed from step 0 to step N
0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times
0 ~ 8, 8 indicates the program end. 0~7 indicates the next execution
pattern number after executing the current pattern
-999 ~ 9,999
Time 0 ~ 900 (1 minute per scale)
Communication write in disabled: 0 (default), Communication write in
enabled: 1
o
o
C/linear input (default): 1 ,
F : 0
Except for the thermocouple B, S, R type, all the other thermocouple
type are valid. (0 or 1)
OFF: 0 (default), ON : 1
0: STOP, 1: RUN (default)
0: RUN (default), 1: STOP
0: RUN (default), 1: Temporarily STOP
0: w/o feedback (default), 1: feedback function
0: Stop AT (default), 1: Start AT
Terminals Definitions
65.0 min.
(2.56)
OUT 2/
OUT 1
ALM
RS-485
-
+
+
-
-
+
V
DATA+
V
8
9
11
DTB4824
7
10
1
2
3
4
5
L
N
+
Tc
AC 100~240V
!
RTD
+
50/60 Hz 5VA
IN
+0.6
44.8
mm
-0
+0.02
(1.76)
-0
(in)
DTB4848
DTB4848
65.0 min.
(EVENT & CT selection)
(2.56)
45.0
+0.6
mm
-0
(1.77)
+0.02
(in)
-0
DTB4896
DTB9696
External Dimensions
Dimensions are in millimeter (inch)
DTB4824
44.75 mm
(1.76 in)
44.8 mm
(1.76 in)
48.0 mm
3.4 mm
99.8 mm
(1.89 in)
(0.13 in)
(3.93 in)
DTB4896
44.0 mm
(1.73 in)
44.5 mm
+0.6
0
(1.75 in)
+0.02
0
48.0 mm
12.8 mm
(0.50 in)
(1.89 in)
79.2 mm(3.12 in)
Mounting
Mounting Method
Step 1 : Insert the controller through the panel cutout.
Step 2 : Insert the mounting bracket into the mounting
groove at the top and bottom of the controller
Step 3 : Push the mounting bracket forward until the
bracket stops at panel wall.
Step 4 : Insert and tighten screws on bracket to secure the
controller in place. (The screw torque should be
0.8kgf-cm to 1.5kgf-cm)
DTB4824 Mounting Method:
DTB4848/4896/9696 Mounting Method:
3
2
1
Error Acknowledgement & Display
Communication error code response description:
Error Status 102EH / 4750H
PV read back 1000H / 4700H
0001H
M/A
0002H
8002H
0003H
8003H
0004H
8004H
0005H
N/A
0006H
8006H
0007H
N/A
Display message:
Power ON
PV
DTB series, Firmware V1.50
SV
Output VR type with Event option
Sensor didn't connect
PV
No
SV
Connect
EEPROM error
PV
Error
SV
EEPROM
How to Set Up Current Input
For normal input
DATA-
12
6
-
-
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most updated version at
DTB4848
(NO EVENT & CT)
OUT1
14V
DC
NO
OUT2/
L
1
6
11
or
-
AC 100~240V
ALM3
4~20mA
50/60 Hz
or
NO
5VA
2
7
12
0~10V
-
COM
N
+
14V
DC
ALM 2
13
RTD
3
8
COM
+
3A
+
+
DATA-
ALM 1
4
14
9
250Vac
3A
IN
Tc
RS-485
250Vac
5
10
15
-
-
DATA+
COM
DTB4896/DTB9696
DTB9696RRV
L
DATA+
1
11
AC 100~240V
RS-485
50/60 Hz
2
12
5VA
DATA-
N
SG
ALM2
3
13
Ev1
4
COM
14
OUTPUT2/ALM3
CT
+
Ev2
COM
5
15
ALM1
NC
6
16
5A
14V
DC
250Vac
NO
7
17
COM
-
NC
OUTPUT1
RTD
8
18
5A
+
+
NO
250Vac
-
9
19
14V
DC
or
4~20mA
IN
Tc
or
0~10V
COM
10
20
- -
+
DTB4848
45.0 mm
+0.6
0
+0.02
(1.77 in)
0
48.0 mm
9.5 mm
80.0 mm
(1.89 in)
(0.37 in)
(3.15 in)
DTB9696
+0.6
91.0 mm
0
(3.58 in)
+0.02
0
96.0 mm
15.8 mm
79.2 mm
(3.78 in)
(0.62 in)
(3.12 in)
Mounting Bracket Installation
CT Wiring Method (if CT function is selected)
Error status
PV unstable
Re-initial, no temperature at this time
Input sensor did not connect
Input signal error
Over input range
ADC fail
EEPROM read/write error
Normal display
Present value
Set value
Input error
Error
Input
Input over range
PV flash when over
For current input (4 ~ 20mA, 0 ~ 20mA)
http://www.delta.com.tw/industrialautomation

Advertisement

loading

This manual is also suitable for:

Dtb4848Dtb4896Dtb9696Dtb seriesDtb4848