Burnham K2WT Residential Installation, Operating And Service Instructions page 142

Table of Contents

Advertisement

XIV. Troubleshooting
E. Active Fault Screen Faults
Indication
Limit String Status
Sensor Status
Rate Limit
EMS Status
142
(continued)
Condition
The Limit String Status screen shows the safety limit status. A contact icon, either
"open" or "closed", graphically represents each safety limit. The "closed" contact icon
is steady; the "open" contact icon is blinking. For example, the screen shown to the
left illustrates a "closed" external limit contact and an "open' LWCO contact.
Limit String
Fault
NOTE: Since the limit string items are wired in series, all limits downstream of the
"open" limit will also appear on the screen as "open" (blinking) icons regardless of
whether or not they are actually open. The Air Proving Switch is wired independent to
all other limits. The Air Proving Switch is only required to be closed during boiler pre-
purge. It is normal for it to be open during run mode.
The Sensor Status screen shows the status of all sensors. Possible states include:
None:
Feature requiring this sensor has not been selected.
Normal: Sensor is working normally.
Shorted: Sensor is shorted or is defective.
Open:
There is a break in the wiring between the Control and the sensor or the
sensor is defective
Sensor Fault
Out of Range: Sensor is defective or is being subjected to electrical noise.
Unreliable:
When a sensor fails "opened" or "shorted" the value is changed to reverse video
(background black and value white) "024" or "768" respectively to indicate that there
is a fault with the sensor.
The following messages appear when the firing rate is limited or reduced to help avoid
a lockout or save energy.
Refer to Hard Lockout section for corrective actions
-
High Stack Temperature Limit
-
High Supply Temperature Limit
-
High Differential Temperature Limit
The following messages appear as part of normal start and stop sequences:
-
Minimum Modulation (normal start/stop sequence)
Rate Limit
-
Low Fire Hold Rate: Low fire hold rate is a normal start-up rate hold used to help
ensure system temperature feedback prior to release to modulation. Low Fire
Hold Time may be adjusted. Refer to the "Changing Adjustable Parameters",
Paragraph F, for additional information.
-
Maximum Expected Heat Rate: Maximum Expected Heat Rate limit is a normal
start-up rate hold used to save energy. This limit helps reduce extra cycles
and save energy. Boiler is free to modulate up to the sum of the active zones and
domestic hot water expected heat rates. Each zone heat rate is adjustable and
may be modified under the modulation menu. Refer to the "Changing Adjustable
Parameters", Paragraph F, for additional information.
The Energy Management System (EMS) fault screen provides input fault status. When
an input is shown as "Not Selected" it is not required for this application or has not yet
been selected. These options are selected under the "Energy Management" Adjust
mode menu.
Energy
Modbus Input Failure
Management
System Fault
4-20mA Input Failure
Possible Cause
Sensor is defective or is being subjected to electrical noise.
If a modus input is selected and out of range or not present
a "535" value is shown reverse video (background black and
value white). To fix the problem check the input source and
check that the input is properly connected.
Failure status for the 4-20mA input is the same as shown
under Sensor Fault.
107672-03 - 5/18