XII. Operation
F. Changing Adjustable Parameters (continued)
"Press"
Factory
Range /
Setting
Choices
Local,
Local
4-20mA
Local,
Local
4-20mA
130°F
80°F (26.7°C) -
Central Heat
Setpoint
(54.4°C)
180°F
80°F (26.7°C) -
Central Heat
Setpoint
(82.2°C)
Local,
Local
Modbus
* Only visible when Central Heat Setpoint Source is set to 4-20mA.
132
button to access the following parameters:
Central Heat Modulation Source
This parameter enables the 4-20mA input to control firing rate and the thermostat input to control
boiler on/off demand directly without using the internal setpoint. The 4-20mA selection is used to
enable a remote multiple boiler controller:
Local:
4-20mA Input on Control Terminals J8-6 and J10-8 is ignored.
4-20mA
4-20mA Input on Control Terminals J8-6 and J10-8 is used to control firing Rate %
directly.
Modbus
Modbus input used to control firing Rate % directly.
Central Heat Setpoint Source
Sets the remote (Energy Management System) control mode as follows:
Local:
Local setpoint and modulation rate is used. 4-20mA input on Control Terminals J8-6 and
J10-8 is ignored.
4-20mA
4-20mA Input on Control Terminals J8-6 and J10-8 is used as the temperature setpoint.
The following two parameters may be used to adjust the signal range.
Modbus
Modbus is used as the temperature setpoint.
Central Heat 4-20mAdc Setup, 4 mA Water Temperature*
Sets the Central Heat Temperature Setpoint corresponding to 4mA for signal input on Control
Terminals J8-6 and J10-8. Current below 4mA is considered invalid, (failed or incorrect wired input).
Central Heat 4-20mAdc Setup, 20 mA Water Temperature*
Sets the Central Heat Temperature Setpoint corresponding to 20mA for signal input on Control
Terminals J8-6 and J10-8. Current above 20mA is considered invalid, (failed or incorrect wired input).
Central Heat Demand Source
This parameter enables a Modbus input to be take the place of the Heating Thermostat Input:
Local
Local Heating Thermostat input is used for Central Heat demand.
Modbus
Modbus input is used for Central Heat demand.
Parameter and Description
107672-03 - 5/18