C.

MASTER/SLAVE WIRING

Connecting Master and Slave units is fast and easy:
Master/Slave connections are made through the SLAVE I/O terminal block (TB1), located at
the top right corner of the gate operator controller board (see Figure 15, below).
Connect the Receive inputs (RECV1, RECV2) on each board to the Transmit inputs (XMIT1,
XMIT2) on the other board.
To prevent cross-talk between Master/Slave wires and power or input wires, use shielded
cable or run the Master/Slave wires in a separate conduit.
Use two 18-14 AWG twisted pair wires or a shielded cable containing 2 twisted pair wires for
Master/Slave Interconnection.
To ensure a reliable communication between Master and Slave units, the maximum allowable
wire length is 3000 feet.
Be sure to connect the two units correctly. Improper wiring of the Master/Slave inter-
connection prevents proper operation of the system.
Figure 15. Master/Slave Connection and Switch S1 Location.
Rev C
NOTE
Doc 6001242 (01-20273)
25 of 53