To Install The Outdoor Unit; To Provide Drainage - Daikin EBLQ-C2V3 Installer's Reference Manual

Altherma monobloc compact outdoor unit
Table of Contents

Advertisement

6 Installation
6.3.4

To install the outdoor unit

CAUTION
Do NOT remove the protective cardboard before the unit is
installed properly.
1 Lift the outdoor unit.
2 Install the outdoor unit as follows:
Installer reference guide
14
a
1
a
Air outlet
NOTICE
Properly align the unit. Make sure the backside of the unit
does NOT protrude.
3 Remove the protective cardboard and instruction sheet.
b
a
a
Protective cardboard
b
Instruction sheet
NOTICE
To prevent damage to the supporting feet, do NOT tilt the
unit sideways in any way:
6.3.5

To provide drainage

▪ Avoid installation places where water leaking from the unit due to
a blocked drain pan can cause damage to the location.
▪ Make sure that condensation water can be evacuated properly.
▪ Install the unit on a base to make sure that there is proper
drainage in order to avoid ice accumulation.
▪ When the unit is in cooling mode, condensate may also form in
the hydro part. When providing drainage, therefore make sure to
cover the entire unit.
▪ Prepare a water drainage channel around the foundation to drain
waste water away from the unit.
▪ Avoid drain water flowing over the footpath, so that it does NOT
become slippery in case of ambient freezing temperatures.
▪ If you install the unit on a frame, install a waterproof plate within
150  mm of the bottom side of the unit in order to prevent water
from getting into the unit and to avoid drain water dripping (see the
following figure).
Daikin Altherma monobloc compact outdoor unit
a
a
2
3
4
EBLQ05+07C2V3
4P598847-1 – 2019.10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eblq05c2v3Eblq07c2v3

Table of Contents