To Start And Stop Forced Cooling - Daikin EBLQ-C2V3 Installer's Reference Manual

Altherma monobloc compact outdoor unit
Table of Contents

Advertisement

2 Carry out forced cooling. See
cooling" [ 4  21].
3 After 5 to 10 minutes (after only 1 or 2 minutes in case of very
low ambient temperatures (<−10°C)), close the liquid stop valve
with a hexagonal wrench.
4 Check on the manifold if the vacuum is reached.
5 After 2-3  minutes, close the gas stop valve and stop forced
cooling.
b
c
a
d
e
d
a
Gas stop valve
b
Closing direction
c
Hexagonal wrench
d
Valve cap
e
Liquid stop valve
11.3

To start and stop forced cooling

Confirm that DIP switch SW2 is in COOL mode.
1 Press the forced cooling operation switch SW1 to begin forced
cooling.
2 Press the forced cooling operation switch SW1 to stop forced
cooling.
COOL
HEAT
NOTICE
Take care that while running forced cooling operation, the
water
temperature
remains
temperature read out of the indoor unit). You can achieve
this, for example, by activating all fans of the fan coil units.
EBLQ05+07C2V3
Daikin Altherma monobloc compact outdoor unit
4P598847-1 – 2019.10
"11.3  To start and stop forced
higher
than
5°C
(see
11 Disposal
Installer reference guide
21