External Signal Output Function - Mitsubishi Electric AG-150A-A Installation Manual

Air-conditioner control system
Hide thumbs Also See for AG-150A-A:
Table of Contents

Advertisement

(4) Recommended circuit
(A) For level signal
This unit
(B) For pulse signal
CN5
Red
9
Gray
8
Blue
7
Yellow
6
Orange
5
1
Max.10m
(32 ft)
This unit
1 The contact relay, DC power source, extension cable, etc., must be prepared on site.
2 The connection cable can be extended up to 10m (32 ft). Use a 0.3mm
3 Strip the extra cable near the connector, and insulate the exposed section securely with tape, etc.

2. External signal output function

* External signal output requires the external I/O adapter PAC-YG10HA (sold separately).
NOTE
* When using a PAC-YG50ECA Expansion controller, connect the external input/output adapter to the external input terminal on
the Expansion controller, not to the AG-150A.
(1) External output
When one or more air conditioners are operating, the "ON" signal will be output, if a malfunction occurs in one or more air
conditioners, the "Malfunction" signal will be output.
(2) External output specifications
CN5
Lead wire
No.1 Green
Common (External ground)
No.2 Black
ON/OFF*
No.3 Brown
Malfunction/normal
(3) Recommended circuit
CN5
9
4
Brown
3
Black
2
Green
1
Max.10m
(32 ft)
This unit
1 Each element will turn on while in ON operation or if a malfunction occurs.
2 The connection cable can be extended up to 10m (32 ft).
3 The relays, lamps, diodes and extension cables, etc, must be prepared separately on site.
CN5
Red
9
8
7
6
Orange
5
1
Max.10m
(32 ft)
Power supply
(12VDC or 24VDC)
Y2
Y1
X1
X2
X2
X1
Run
Stop
Details of each terminal
Diode (*2)
Z1
(*2)
Z2
(*2)
Z1
Z2
Power (*1)
Supply
L1: Run display lamp
L2: Malfunction display lamp
X1
Run/stop or
Emergency stop
X1
Power supply
(12VDC or 24VDC)
Y1
Y2
Prohibit Enable
* The operation status of DIDO controller is not output.
* Operation signal is output during an error.
Use Z1 and Z2 relays that meet the following specifications.
Operation coil
Rated voltage:
Power Consumption: 0.9W or less
(*1) Prepare a power supply separately according to the
L1
relay being used (12VDC or 24VDC).
(*2) Always include a diode on both ends of the relay coil.
L2
Important
• Be sure to use 12VDC or 24VDC for a power supply.
• Connect the power supply with correct polarity.
• Do not connect the power supply without relays
being connected to the controller. (no load)
Improper connection may result in malfunctions.
- 27 -
Use relays X1, X2, Y1, and Y2 that meet the
following specifications.
Contact rating
Rated voltage >=12VDC
Rated current >= 0.1A
Minimum applicable load =< 1mA at DC
Important
• Be sure to use 12VDC or 24VDC for a
power supply.
• Connect the power supply with correct
polarity.
Improper connection may result in malfunctions.
2
(AWG 22) or larger wire.
12VDC, 24VDC