For all steps in this section, when tightening terminals, apply the correct torque.
Aux Inputs: 3.5 to 4.4 in-lb (0.4 to 0.5 N-m); all other terminals: 4.4 to 5.3 in-lb (0.5 to 0.6 N-m).
1. Wire the CTs to the E31E. Note: For Veris CTs, X1 is the white lead, X2 is the black lead.
2. Connect 2-wire 100-277 VAC power to the control power terminals. Observe polarity. Connect voltage lines to the voltage taps.
Equip voltage lines with fuses and disconnects as required.