Installation Guide
Power Monitoring
E31E Series
Installation (cont.)
Z206855-0B
Page 10 of 26
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
1.888.610.7664
8. The adapter boards are silk screened with two rows of numbers. For applications that require odd/even branch circuit
numbering, use the row designated ODD or EVEN. For applications that require sequential numbering, use the number row
marked SEQ.
BLACK
WHITE
ODD
SEQ
Adapter Board A numbering:
ODD
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41
SEQ
21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
BLACK
WHITE
EVEN
SEQ
Adapter Board B numbering:
EVEN
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
SEQ
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
9. Connect 0.333VAC current transducers (CTs) to the conductors to be monitored by snapping CTs around lines, observing local
codes regarding bending radius.
Panel 2
Panel 1
Note: The E31E measures and reports the phase angle of each voltage input and each CT (when there is active current
through the primary of that CT). Use the E3x Configuration Tool to view the phase angles of active circuits to help verify
that those circuits are connected to and mapped to the proper voltage phases. See the E3x Commissioning Guide for
instructions on how to download and operate the tool from a PC.