Frequency setting by analog input (terminal 1, 2, 4)
⋅ Refer to the following table and set Pr. 73 and Pr. 267. (
AU
Terminal 4 Input
signal
OFF
Pr. 267 setting
0
(initial
4 to 20mA
value)
1
1 to 5V *
ON
2
2 to 10V *
* If the input specification to terminal 4 is changed from the current input (Pr. 267 = "0") to the 0 to 5V or 0 to 10V voltage input (Pr. 267 ="1 or
2"), calibrate the input with C6. (Refer to page 179)
⋅ Set the voltage/current input switch referring to the table below.
indicates an initial value.)
(
Terminal 2 Input
Specifications
Voltage input (0 to 10V)
0, 2, 4, 10, 12, 14
Voltage input (0 to 5V)
1 (initial value), 3, 5, 11, 13, 15
Current input (0 to 20mA)
6, 7, 16, 17
CAUTION
⋅ Turn the AU signal ON to make terminal 4 valid.
⋅ Match the setting of parameter and switch. A different setting may cause a fault, failure or malfunction.
⋅ The terminal 1 (frequency setting auxiliary input) signal is added to the main speed setting signal of the terminal 2 or 4.
⋅ When an override is selected, the terminal 1 or 4 is used for the main speed setting and the terminal 2 for the override signal
(50% to 150% at 0 to 5V or 0 to 10V). (When the main speed of the terminal 1 or terminal 4 is not input, compensation by the
terminal 2 is invalid.))
⋅ Use Pr. 125 (Pr. 126) (frequency setting gain) to change the maximum output frequency at input of the maximum output frequency
command voltage (current). At this time, the command voltage (current) need not be input.
Also, the acceleration/deceleration time, which is a slope up/down to the acceleration/deceleration reference frequency, is not
affected by the change in Pr. 73 setting.
⋅ When Pr. 22 Stall prevention operation level = "9999", the value of the terminal 1 is as set to the stall prevention operation level.
⋅ When Pr. 561 PTC thermistor protection level ≠ "9999", terminal 2 is not available for analog frequency command.
174
Terminal 2
Pr. 73
Setting
Input
0
0 to 10V
1
0 to to 5V
(initial value)
2
0 to 10V
3
0 to 5V
4
0 to 10V
5
0 to 5V
6
0 to 20mA
7
0 to 20mA
10
0 to 10V
11
0 to 5V
12
0 to 10V
13
0 to 5V
14
0 to 10V
15
0 to 5V
16
0 to 20mA
17
0 to 20mA
0
1
(initial value)
2
3
4
0 to 10V
5
0 to 5V
6
7
10
11
12
13
14
0 to 10V
15
0 to 5V
16
17
Pr. 73 Setting
Switch 2
OFF
OFF
indicates the main speed setting)
Compensation Input
Terminal 1
Terminal and
Input
Compensation Method
0 to ±10V
0 to ±10V
Terminal 1
Added compensation
0 to ±5V
0 to ±5V
0 to ±10V
Terminal 2
0 to ±5V
Override
0 to ±10V
0 to ±5V
0 to ±10V
Terminal 1
0 to ±10V
Added compensation
0 to ±5V
0 to ±5V
0 to ±10V
Terminal 2
0 to ±5V
Override
0 to ±10V
Terminal 1
0 to ±5V
Added compensation
0 to ±10V
0 to ±10V
Terminal 1
Added compensation
0 to ±5V
0 to ±5V
Terminal 2
Override
0 to ±10V
0 to ±5V
0 to ±10V
Terminal 1
0 to ±10V
Added compensation
0 to ±5V
0 to ±5V
Terminal 2
Override
0 to ±10V
Terminal 1
0 to ±5V
Added compensation
Terminal 4 Input
Specifications
Voltage input (0 to 10V)
Voltage input (0 to 5V)
ON
Current input (0 to 20mA)
Polarity Reversible
No
(Indicates that a
frequency command
signal of negative
polarity is not
accepted.)
Yes
No
(Indicates that a
frequency command
signal of negative
polarity is not
accepted.)
Yes
⎯ : Invalid
Pr. 267 Setting
2
1
0 (initial value)
Switch 1
OFF
OFF
ON

Advertisement

Table of Contents
loading

Table of Contents