Modbus Point Map Overview; Modbus Point Map - Veris Industries E50C A Series Installation Manual

Compact power and energy meter
Table of Contents

Advertisement

Installation Guide
Power Monitoring
E50B1A, E50C2A, E50C3A

Modbus Point Map

Overview
ZL0116-0A
Page 18 of 26
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
The E50C2A Full Data Set (FDS) features data outputs such as demand calculations, per phase VA and VAR, and VAh VARh
accumulators. The E50C3A data logging model adds configuration registers 155-178 and buffer reading at registers 8000-13760.
For security reasons, configuration and resets on all E50 models are protected by a user configurable passcode. The meter supports
variable CTs and PTs, allowing a much wider range of operation from 90V x 5A up to 32000V x 5000A. To promote this, the meter
permits variable scaling of the 16-bit integer registers via the scale registers. The 32-bit floating point registers do not need to be
scaled.
Integer registers begin at 001 (0x001). Floats at 257 (0x101). Configuration registers at 129 (0x081). Values not supported in a
particular System Type configuration will report QNAN (0x8000 in Integer Registers, 0x7FC00000 in Floating Point Registers).
Supported Modbus Commands
Note: ID String information varies from model to model. Text shown here is an example.
Command
0x03
Read Holding Registers
0x04
Read Input Registers
0x06
Preset Single Register
0x10
Preset Multiple Registers
Report ID
Return string:
byte0: address
byte1: 0x11
0x11
byte2: #bytes following w/out crc
byte3: ID byte = 247
byte4: status = 0xFF if the operating system is used; status = 0x00 if the reset system is used
bytes5+: ID string = "Veris Industries E50xxA Power Meter Full Data Set" or "Veris Industries E50xxA Power Meter - RESET
SYSTEM RUNNING RS Version x.xxx" last 2 bytes: CRC
Read Device Identification, BASIC implementation (0x00, 0x01 and 0x02 data), Conformity Level 1.
Object values:
0x01: "Veris Industries"
0x2B
0x02: " E50xxA"
0x03: "Vxx.yyy", where xx.yyy is the OS version number (reformatted version of the Modbus register #7001, (Firmware
Version, Operating System).
If register #7001 == 12345, then the 0x03 data would be "V12.345").
Legend
The following table lists the addresses assigned to each data point. For floating point format variables, each data point appears
twice because two 16-bit addresses are required to hold a 32-bit float value.
R/W
R=read only; R/W=read from either int or float formats, write only to integer format.
NV
Value is stored in non-volatile memory. The value will still be available if the meter experiences a power loss and reset.
UInt
Unsigned 16-bit integer.
SInt
Signed 16-bit integer.
Format
ULong
Unsigned 32-bit integer; Upper 16-bits (MSR) in lowest-numbered / first listed register (001/002 = MSR/LSR).
Float
32-bit floating point; Upper 16-bits (MSR) in lowest-numbered / first listed register (257/258 = MSR/LSR). Encoding
is per IEEE standard 754 single precision.
Units
Lists the physical units that a register holds.
Some Integer values must be multiplied by a constant scale factor (typically a fraction), to be read correctly. This is done to allow
Scale Factor
integer numbers to represent fractional numbers.
Range
Defines the limit of the values that a register can contain.
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Description
TM
07132

Advertisement

Table of Contents
loading

This manual is also suitable for:

E50b1aE50c2aE50c3aE50cxa

Table of Contents