Veris Industries E50C1A Installation Manual page 13

Compact power and energy meter for use only with e683 series rope cts
Table of Contents

Advertisement

E50C1A Installation Guide
UI for Setup
To Setup p. 2 "SPASS"
Back
From:
SETUP > PASWD
Back
Current
Transformer
Back
System
Type
Back
Potential
Transformer
Back
Sytem
Voltage
Back
Sytem
Voltage
To Setup p. 2 "SPLOS"
† When leaving this parameter screen using the right button ( ), the display will
briefly indicate "SAvEd)" to confirm that any changes made have been accepted.
ZL0124-0E
Page 13 of 20
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
RS-485
Output
ADDR
S COM
--------
001
CT V
--------
S CT
1.0
.33
SYSTM
--------
3L-1n
S SYS
3L
2L-1n
2L
1L-1n
Next
RATIO
S PT
--------
001.00
Next
V LL
S
V
--------
00600
Next
MX KW
S PWR
--------
103.92
Next
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
BAUD
--------
PAR
38400
--------
19200
nOnE
9600
EvEn
4800
Odd
2400
1200
Next
CT SZ
Set Current Transducer:
--------
CT V - CT Input Voltage: + or – to Select 1.0 or .33V.
100
CT SZ - CT Size: in Amps. Maximum is 32000 Amps.
Next
Set System Configuration:
SYSTM: + or – to step through the following System Type options:
System
Reg 130 CTs Description
3L-1n
40
3
Wye Three Phase: A, B, & C with Neutral (Default).
3L
31
3
Delta Three Phase: A, B & C; no Neutral
2L-1n
12
2
Single Split Phase: A & B with Neutral
2L
11
1
Single Phase: A & B; no Neutral
1L-1n
10
1
Single Phase: A to Neutral
Set Potential Transfomer Ratio:
RATIO – Potential transformer step down is RATIO:1. Default is 1:1
(No PT installed). See Install for wiring diagrams. This value must be
set before the System Voltage (if used).
Set System Voltage:
V LL – The nominal Line to Line Voltage for the system. This is used
by the meter to calculate the theoretical maximum system power, and
as the reference voltage for setting the Phase Loss threshold.
Maximum is 32000 Volts. For system type 1+N (10), this is a Line to
Neutral Voltage, indicated by "V LN". Note: the meter will reject settings
that are not within the meter's operating range when divided by the PT
ratio.
System Power:
MX KW – The theoretical Maximum System Power is calculated by the
meter from the System Voltage, CT size, and System Type. Power
Factor is assumed to be unity. The value of System Power is used to
determine which combinations of pulse weight and duration are valid
and will keep up with the maximum power the meter will see. This value
is read only.
Set Communications Parameters:
ADDR - Modbus Address: 1 – 247.
+ increments the selected (blinking) digit.
- selects the digit to the left.
BAUD - Baud Rate: 1200 – 38400 Baud
PAR - Parity: Odd, Even, None
+
or
to step through the options.
Note: Bold is the Default.