Power Monitoring
Analog_Input Objects (cont.)
#
Object
Description
Name
AI38
KVARh_Q1_B
Reactive Energy Q1
Phase b
AI39
KVARh_Q1_C
Reactive Energy Q1
Phase C
AI40
KVARh_Q2_A
Reactive Energy Q2
Phase A
AI41
KVARh_Q2_B
Reactive Energy Q2
Phase B
AI42
KVARh_Q2_C
Reactive Energy Q2
Phase C
AI43
KVARh_Q3_A
Reactive Energy Q3
Phase A
AI44
KVARh_Q3_B
Reactive Energy Q3
Phase B
AI45
KVARh_Q3_C
Reactive Energy Q3
Phase C
AI46
KVARh_Q4_A
Reactive Energy Q4
Phase A
AI47
KVARh_Q4_B
Reactive Energy Q4
Phase b
AI48
KVARh_Q4_C
Reactive Energy Q4
Phase C
AI49
KVAh_
Apparent Energy
Import_A
Import Phase A
AI50
KVAh_
Apparent Energy
Import_B
Import Phase B
AI51
KVAh_
Apparent Energy
Import_C
Import Phase C
AI52
KVAh_
Apparent Energy
Export_A
Export Phase A
AI53
KVAh_
Apparent Energy
Export_B
Export Phase B
AI54
KVAh_
Apparent Energy
Export_C
Export Phase C
AI55
KW_A
Real Power Phase A
AI56
KW_B
Real Power Phase B
AI57
KW_C
Real Power Phase C
AI58
KVAR_A
Reactive Power
Phase A
AI59
KVAR_B
Reactive Power
Phase B
AI60
KVAR_C
Reactive Power
Phase C
AI61
KVA_A
Apparent Power
Phase A
AI62
KVA_B
Apparent Power
Phase B
ZL0123-0D
Page 27 of 32
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
R/W
NV
Units
R
NV
kVARh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
NV
kVAh
0 - 3.4+E38
R
NV
kVAh
0 - 3.4+E38
R
NV
kVAh
0 - 3.4+E38
R
NV
kVAh
0 - 3.4+E38
R
NV
kVAh
0 - 3.4+E38
R
NV
kVAh
0 - 3.4+E38
R
kW
0 - Max_Power (AI76)
R
kW
0 - Max_Power (AI76)
R
kW
0 - Max_Power (AI76)
R
kVAR
0 - Max_Power (AI76)
R
kVAR
0 - Max_Power (AI76)
R
kVAR
0 - Max_Power (AI76)
R
kVA
0 - Max_Power (AI76)
R
kVA
0 - Max_Power (AI76)
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Range
The Units property of object AI38 reports that these units are kWh because there
is no unit type in the BACnet standard for kVARh
The Units property of object AI39 reports that these units are kWh because there
is no unit type in the BACnet standard for kVARh
The Units property of object AI40 reports that these units are kWh because there
is no unit type in the BACnet standard for kVARh
The Units property of object AI41 reports that these units are kWh because there
is no unit type in the BACnet standard for kVARh
The Units property of object AI42 reports that these units are kWh because there
is no unit type in the BACnet standard for kVARh
The Units property of object AI43 reports that these units are kWh because there
is no unit type in the BACnet standard for kVARh
The Units property of object AI44 reports that these units are kWh because there
is no unit type in the BACnet standard for kVARh
The Units property of object AI45 reports that these units are kWh because there
is no unit type in the BACnet standard for kVARh
The Units property of object AI46 reports that these units are kWh because there
is no unit type in the BACnet standard for kVARh
The Units property of object AI47 reports that these units are kWh because there
is no unit type in the BACnet standard for kVARh
The Units property of object AI48 reports that these units are kWh because there
is no unit type in the BACnet standard for kVARh
The Units property of object AI49 reports that these units are kWh because there
is no unit type in the BACnet standard for kVAh
The Units property of object AI50 reports that these units are kWh because there
is no unit type in the BACnet standard for kVAh
The Units property of object AI51 reports that these units are kWh because there
is no unit type in the BACnet standard for kVAh
The Units property of object AI52 reports that these units are kWh because there
is no unit type in the BACnet standard for kVAh
The Units property of object AI53 reports that these units are kWh because there
is no unit type in the BACnet standard for kVAh
The Units property of object AI54 reports that these units are kWh because there
is no unit type in the BACnet standard for kVAh