Veris Industries E51H2A Installation Manual page 25

Bi-directional compact power and energy meter with bacnet ms/tp support for use only with e683 series rope cts
Table of Contents

Advertisement

Installation Guide
Power Monitoring
Analog_Input Objects
#
Object
Description
Name
AI1
KWh_Net
Accumulated Real
Energy: Net (Import -
Export)
AI2
KWh_Import
Real Energy Import
AI3
KWh_Export
Real Energy Export
AI4
KVARh_Q1
Reactive Energy
Quadrant 1
AI5
KVARh_Q2
Reactive Energy
Quadrant 2
AI6
KVARh_Q3
Reactive Energy
Quadrant 3
AI7
KVARh_Q4
Reactive Energy
Quadrant 4
AI8
Net_KVAh
Apparent Energy: Net
(Import - Export)
AI9
KVAh_Import
Apparent Energy
Import
AI10
KVAh_Export
Apparent Energy
Export
AI11
KW_Total
Total Instantaneous
Real Power
AI12
KVAR_Total
Total Instantaneous
Reactive Power
AI13
KVA_Total
Total Instantaneous
Apparent Power
AI14
PF_Total
Total Power Factor
AI15
Volts_LL_Avg
Voltage, L-L, Average
of Active Phases
AI16
Volts_LN_Avg Voltage, L-N, Average
of Active Phases
AI17
Current
Current, Average of
Average
Active Phases
AI18
Frequency
Frequency
ZL0123-0D
Page 25 of 32
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Use the Present_Value property of the Analog_Input objects for all read-only numeric variables in the meter other than those
used specifically for device configuration (in the Device Object) or data logging (in the Trend_Log objects). Only the E51H5A
supports the data logging capability.
These objects support the Description and Reliability object properties and all required Analog_Input object properties. None
of them are writable. The values that are not instantaneous (i.e., Accumulated Energy, Max Demand, Pulse Input Counts) are
non-volatile. They are not updated while control power is inactive, but their past values are retained when power is restored. The
Present_Value of the accumulated data objects (AI1-AI10 and AI31-AI54) use floating-point data types (all AI objects use floating
point data points). The resolution of the accumulated values decreases as the value grows larger over time and more of the
significant digits precede the decimal point. If the size of the value limits the resolution unacceptably, read and store the current
value offline and reset the accumulators to restore finer resolution.
For complete assurance, check the Reliabilty property for a No_Fault_Detected status before reading the Present_Value. If the
line voltage or input frequency of the system being monitored falls out of the supported range, the corresponding alert bits
(BI1-BI7) are set and the reliability property of any values that cannot be accurately measured under those conditions returns
Unreliable_Other.
R/W
NV
Units
R
NV
kWh
-3.4+E38 - 3.4+E38
R
NV
kWh
0 - 3.4+E38
R
NV
kWh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
NV
kVAh
-3.4+E38 - 3.4+E38
R
NV
kVAh
0 - 3.4+E38
R
NV
kVAh
0 - 3.4+E38
R
kW
0 - Max_Power (AI76)
R
kVAR
0 - Max_Power (AI76)
R
kVA
0 - Max_Power (AI76)
R
-1.00 - 1.00
R
Volts
R
Volts
R
Amps
R
Hz
45.0 - 65.0
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Range
The Units property of object AI4 reports that these units are kWh because there
is no unit type in the BACnet standard for KVARh
The Units property of object AI5 reports that these units are kWh because there
is no unit type in the BACnet standard for kVARh
The Units property of object AI6 reports that these units are kWh because there
is no unit type in the BACnet standard for kVARh
The Units property of object AI7 reports that these units are kWh because there
is no unit type in the BACnet standard for kVAh
The Units property of object AI8 reports that these units are kWh because there
is no unit type in the BACnet standard for kVAh
The Units property of object AI9 reports that these units are kWh because there
is no unit type in the BACnet standard for kVAh
The Units property of object AI10 reports that these units are kWh because there
is no unit type in the BACnet standard for kVAh
Returns QNAN if frequency is out of range (or no voltage input present on Phase
A)
Additional Information