4. SERVICE PROCEDURES
C. Check "Operation selector" switch in the indoor unit.
: In case of wireless remote control unit
• Has "Operation selector"
switch been set to ON
position ?
Set "Operation selector"
switch to ON.
Switch Ass'y or P.C.B.
Ass'y in the indoor unit
is defective.
D. Check compressor motor protectors.
a)
High pressure switch (63PH)
• Check high pressure switch.
Does high pressure switch
actuate ?
• Is outdoor heat exchanger
coil dirty or are there
obstacles near air suction
inlet of outdoor unit ?
• Check if outdoor fan rotates.
Refer to "Only outdoor fan
does not run."
b)
Compressor motor overcurrent relay (51C)
• Check compressor motor
overcurrent relay. (51C)
Does it actuate ?
• Check power supply voltage.
Is voltage 90% or less of
rated voltage ?
• Following causes may be considered.
Locked rotor of compressor.
Overcharged refrigerant.
Air shortage of outdoor unit ventilation.
Obstacles in front of outdoor unit.
YES
NO
But neither unit runs.
(63PH)
YES
YES
NO
NO
Refer to "CHECKING ELECTRICAL COMPONENTS
(Electro magnetic contactor)".
YES
YES
90% or more of
NO
rated voltage.
Disconnect the socket from 2P (WHT) connector.
Check the continuity between No.1 and No.2 poles
of the socket.
Consult power supply company
and restore voltage to
normal value.
45
IND. LAMP Ass'y or P.C.B.
Ass'y in the indoor unit
is defective.
0617_X_S
Clean heat exchanger coil
or remove obstacles.
0618_X_S