Connecting The Electrical Wiring; About Electrical Compliance; Specifications Of Standard Wiring Components; To Connect The Electrical Wiring On The Outdoor Unit - Daikin RZQG71L8Y1L Installation Manual

Split system air conditioners
Hide thumbs Also See for RZQG71L8Y1L:
Table of Contents

Advertisement

4 Installation
4.5

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
For use of units in applications with temperature alarm
settings it is recommended to foresee a delay of 10
minutes for signalling the alarm in case the alarm
temperature is exceeded. The unit may stop for several
minutes during normal operation for "defrosting the unit", or
when in "thermostat stop" operation.
4.5.1

About electrical compliance

RZQG71_V1 + RZQG100~140_Y1
Equipment complying with:
▪ EN/IEC 61000‑3‑12 provided that the short-circuit power S
greater than or equal to the minimum S
point between the user's supply and the public system.
▪ EN/IEC
61000‑3‑12
=
Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input
current >16 A and ≤75 A per phase.
▪ It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply
with a short-circuit power S
minimum S
value.
sc
Model
RZQG71_V1 + RZQG100~140_Y1
4.5.2
Specifications of standard wiring
components
Component
(a)
Power supply
MCA
cable
Voltage
Phase
Frequency
Wire sizes
Interconnection cables
Recommended field fuse
Earth leakage circuit breaker
(a)
MCA=Minimum circuit ampacity. Stated values are
maximum values (see electrical data of combination with
indoor units for exact values).
Installation manual
8
sc
value at the interface
sc
European/International
Technical
greater than or equal to the
sc
Minimum S
value
sc
1170 kVA
V1
Y1
71
71
100
125+140
20.6 A 14.0 A 21.0 A
22.5 A
230 V
400 V
1~
3N~
50 Hz
Must comply with applicable
legislation
Minimum cable section of 2.5
mm² and applicable for 230 V
25 A
16 A
25 A
Must comply with applicable
legislation
4.5.3
To connect the electrical wiring on the
outdoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1 Remove the service cover.
2 Connect the interconnection cable and power supply as follows:
c
d
is
e
a
Interconnection cable
b
Power supply cable
c
Earth leakage circuit breaker
d
Fuse
e
User interface
V1
c
d
e
f
a
Switch box
b
Stop valve attachment plate
c
Earth
d
Cable tie
e
Interconnection cable
f
Power supply cable
3 Fix the cables (power supply and interconnection cable) with a
cable tie to the stop valve attachment plate.
RZQG71L9V1L + RZQG71~125L8Y1L + RZQG140L7Y1L
V1
Y1
1~50 Hz
3N~50 Hz
220-240 V
380-415 V
L1 L2 L3
b
L1 L2 L3
N
a
a
b
Y1
c
c
d
e
f