F97CMN and G97CMN: Installation, Start-up, Operating and Service and Maintenance Instructions
19. Turn on gas supply and cycle furnace through one complete heating
cycle. Verify the furnace temperature rise as shown in Adjustments
Section. Adjust temperature rise as shown in Adjustments Section.
Fig. 65 – Blower Assembly
NOTE: Be sure to attach ground wire and reconnect blower harness
plugs to blower motor.
Cleaning Burners and Flame Sensor
The following items must be performed by a qualified service
technician. If the burners develop an accumulation of light dirt or dust,
they may be cleaned by using the following procedure:
NOTE: Use a back-up wrench on the gas valve to prevent the valve
from rotating on the manifold or damaging the mounting to the burner
assembly.
WARNING
!
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Turn off the gas and electrical supplies to the furnace and install lockout
tag before performing any maintenance or service. Follow the operating
instructions on the label attached to the furnace.
Refer to
Fig.
59.
1. Disconnect power at external disconnect, fuse or circuit breaker.
2. Turn off gas at external shut-off or gas meter.
3. Remove control door and set aside.
4. Turn electric switch on gas valve to OFF.
5. Disconnect the gas pipe from gas valve and remove pipe from the
furnace casing.
6. Disconnect the connector harness from gas valve (Modulating only)
or remove individual wires from terminals on gas valve (All other
models).
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7. Disconnect Hot Surface Igniter (HSI) wires from HSI.
8. Disconnect Flame Sensor wire from Flame Sensor.
BURNER SUPT. ASSY
BURNER ASSY
FLAME SENSOR
(BELOW BURNER)
9. Support the manifold and remove the 4 screws that secure the
manifold assembly to the burner assembly and set aside. Note the
location of the green/yellow wire and ground terminal.
10. Inspect the orifices in the manifold assembly for blockages or
obstructions. Remove orifice and clean or replace orifice.
11. Remove the four screws that attach the top plate of the casing to the
furnace.
12. Raise top plate up slightly and prop it up with a small piece of wood
or folded cardboard.
13. Support the burner assembly and remove the screws that attach the
burner assembly to the heat exchanger cell panel.
14. Remove wires from both rollout switches.
A11584
15. Slide one-piece burner out of slots on sides of burner assembly.
16. Remove the flame sensor from the burner assembly.
17. (Optional) Remove the Hot Surface Igniter (HSI) and bracket from
the burner assembly.
18. Check igniter resistance. Nominal resistance is 40 to 70 ohms at
room temperature and is stable over the life of the igniter.
19. Clean burner with a brush and a vacuum.
20. Clean the flame sensor with fine steel wool (0000 grade). Do not
use sand paper or emery cloth.
To reinstall burner assembly:
1. Install the Hot Surface Igniter (HSI) and bracket in burner
assembly.
2. Install flame sensor on burner.
3. Align the edges of the one-piece burner with the slots in the burner
assembly and slide the burners forward until they are fully seated in
the burner assembly.
4. Align the orifices in the manifold assembly with the support rings
on the end of the burner.
5. Insert the orifices in the support rings of the burners.
NOTE: If manifold does not fit flush against the burner, do not force the
manifold on the burner assembly. The burners are not fully seated
forward in the burner assembly. Remove the manifold and check burner
positioning in the burner assembly before re-installing the manifold.
6. Attach the green/yellow wire and ground terminal to one of the
manifold mounting screws.
7. Install the remaining manifold mounting screws.
8. Check the igniter alignment, see
9. Attach the wires to the roll-out switches.
61
IGNITER
BRACKET, IGNITER
Fig. 66 – Burner Assembly
Fig.
66,
Fig. 67
FLAME ROLLOUT
SWITCH
A11403
and
Fig.
68.

Hide quick links: