Air Ducts; With Filter) - Tempstar F97CMN Installation, Start-Up, Operating And Service And Maintenance Instructions

Modulating, high efficiency condensing gas furnace, 4-way multipoise
Table of Contents

Advertisement

F97CMN and G97CMN: Installation, Start-up, Operating and Service and Maintenance Instructions
than 12-in. (305 mm) above the combustible deck or suspended furnaces
closer than 12-in. (305 mm) to joists. The sheet metal MUST extend
underneath the furnace casing by 1-in. (25 mm) with the door removed.
The bottom closure panel on furnaces of widths 17-1/2-in. (445 mm) and
larger may be used for flame roll-out protection when bottom of furnace
is used for return air connection. See
roll-out shield.

AIR DUCTS

!
Many states, provinces and localities are considering or have
implemented standards and/or restrictions on duct sizing practices,
ductwork leakage, and/or ductwork thermal, airflow and electrical
efficiencies. CONSULT LOCAL CODE OFFICIALS for ductwork
design and performance requirements in your area.
General Requirements
The duct system should be designed and sized according to accepted
national standards such as those published by: Air Conditioning
Contractors Association (ACCA Manual D), Sheet Metal and Air
Conditioning
Contractors
National Association
American Society of Heating, Refrigerating and Air Conditioning
Engineers (ASHRAE) or consult The Air Systems Design Guidelines
reference tables available from your local distributor. The duct system
should be sized to handle the required system design CFM at the design
external static pressure. The furnace airflow rates are provided in
Table
7-Air Delivery-CFM (With Filter). When a furnace is installed so
that the supply ducts carry air circulated by the furnace to areas outside
the space containing the furnace, the return air shall also be handled by
Unit Size: 0601714
Clg/CF Switch settings
Clg Switches
SW2-3
Clg Default:
OFF
CF Switches
SW3-3
Low-Clg Default:
OFF
OFF
OFF
OFF
Cooling Airflow
ON
(SW2)
Low-Cooling
ON
Airflow (SW3)
ON
ON
Maximum Clg Airflow
CF Switches
SW3-3
Cont. Fan Default:
OFF
OFF
OFF
OFF
Continuous Fan
ON
Airflow (SW3)
ON
ON
ON
Maximum Heat Airflow
Heating (SW1)
Intermediate Heat Airflow
Minimum Heat Airflow
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Fig. 25
for proper orientation of
NOTICE
(SMACNA)
4
Table 7 – Cooling
and Heating Air Delivery - CFM (Bottom Return
(SW1-5 and SW4-3 set to OFF, except as indicated. See notes 1 and 2.)
SW2-2
SW2-1
0.1
OFF
OFF
1060
SW3-2
SW3-1
OFF
OFF
545
OFF
ON
545
ON
OFF
710
ON
ON
875
OFF
OFF
1060
OFF
ON
1235
ON
OFF
1235
ON
ON
1235
2
1425
SW3-2
SW3-1
OFF
OFF
545
OFF
ON
545
ON
OFF
710
ON
ON
875
OFF
OFF
1060
OFF
ON
1060
ON
OFF
1060
ON
ON
1060
3
1075
3
535
3
420
duct(s) sealed to the furnace casing and terminating outside the space
containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used. Seal
supply- and return-duct connections to furnace with code approved tape
or duct sealer.
NOTE: Flexible connections should be used between ductwork and
furnace to prevent transmission of vibration.
Ductwork passing through unconditioned space should be insulated to
enhance system performance. When air conditioning is used, a vapor
barrier is recommended.
Maintain a 1-in. (25 mm) clearance from combustible materials to
supply air ductwork for a distance of 36-in. (914 mm) horizontally from
the furnace. See NFPA 90B or local code for further requirements.
Return Duct Sizing
Refer to the Filter Selection and Duct Sizing section for information on
the proper selection of filter sizes and the associated ductwork and duct
transitions. Improperly designed filtering systems and return ductwork
are the most common causes of airflow and/or noise complaints in
HVAC systems.
Ductwork Acoustical Treatment
NOTE: Metal duct systems that do not have a 90 degree elbow and 10
or
ft. (3 M) of main duct to the first branch take-off may require internal
acoustical lining. As an alternative, fibrous ductwork may be used if
constructed and installed in accordance with the latest edition of
SMACNA construction standard on fibrous glass ducts. Both acoustical
lining and fibrous ductwork shall comply with NFPA 90B as tested by
UL Standard 181 for Class 1 Rigid air ducts.
NOTE: For horizontal applications, the top most flange may be bent
past 90?to allow the evaporator coil to hang on the flange temporarily
External Static Pressure (ESP)
0.2
0.3
0.4
0.5
1070
1080
1080
1075
530
520
525
510
530
520
525
510
710
710
695
690
880
890
895
895
1070
1080
1080
1075
1240
1250
1255
1255
1240
1250
1255
1255
1240
1250
1255
1255
1425
1405
1370
1335
530
520
525
510
530
520
525
510
710
710
695
690
880
890
895
895
1070
1080
1080
1075
1070
1080
1080
1075
1070
1080
1080
1075
1070
1080
1080
1075
1085
1095
1095
1090
515
505
515
495
410
415
400
380
20
5

With Filter)

0.6
0.7
0.8
0.9
1065
1050
1035
1025
See note 4
See note 4
See note 4
890
885
880
870
1065
1050
1035
1025
1250
1230
1190
1155
1250
1230
1190
1155
1250
1230
1190
1155
1300
1260
1225
1190
See note 4
See note 4
See note 4
890
885
880
870
1065
1050
1035
1025
1065
1050
1035
1025
1065
1050
1035
1025
1065
1050
1035
1025
1080
1065
1050
1035
See note 4
See note 4
1.0
1010
855
1010
1115
1115
1115
1155
855
1010
1010
1010
1010
1020

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

G97cmn06017140602120080171408021201002122 ... Show all

Table of Contents