F97CMN and G97CMN: Installation, Start-up, Operating and Service and Maintenance Instructions
Condensate Trap-Horizontal Orientation
When the furnace is installed in the horizontal right position, the
condensate trap will be initially located at the bottom left corner of the
collector box, as received from the factory. See the top image in
When the furnace is installed in the horizontal left position, the
condensate trap will be initially located at the top of the collector box, as
received from the factory. See the top image in
trap must be repositioned on the collector box for proper condensate
drainage. See the bottom images in
A field-supplied, accessory Horizontal Installation kit (trap grommet) is
required for all direct-vent horizontal installations (only). The kit
contains a rubber casing grommet designed to seal between the furnace
casing and the condensate trap, see
If alternate vent position
is required, loosen clamp
on vent elbow inlet.
Remove relief tube
from port on collector
box.
Unconverted Factory Trap Configuration
As Viewed in the Horizontal Left Orientation
Rotate elbow to
desired position and
torque clamp on inlet
15 lb.-in.
Slide relief tube in
stand-offs to adjust
length.
Attach condensate
trap to collector box
with screw.
Align trap over middle
and right-hand port on
collector box.
Horizontal Left Trap Configuration
Fig. 9 – Horizontal Left Configuration
(Appearance May Vary)
To Relocate the Condensate Trap:
• Remove the knockout in the casing for the condensate trap.
• Install the grommet in the casing when required for direct-vent
horizontal applications.
• Orient the furnace in the desired position.
• Allow for 2 in. (51 mm) of clearance underneath the furnace for the
condensate trap and drain line.
Fig. 10
shows the condensate trap and tubing before and after
relocation in the horizontal right position.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Fig.
Fig.
9. In both cases, the
Fig. 10
and
Fig.
9.
Fig.
11.
Remove trap from
collector box.
Remove relief tube
from relief port on
condensate trap.
Remove pressure switch tube
from port on collector box.
Remove middle and right
plug from collector box.
DO NOT DISCARD
Install plugs in open
ports on collector box.
Connect relief tube to
port on collector box.
Trim excess tube.
Route pressure switch tube
underneath relief tube and
connect to port on collector box.
Connect relief tube to
relief port on condensate
trap.
Fig. 9
shows the condensate trap and tubing before and after
relocation in the horizontal left position.
• Refer to the appropriate figure to begin the trap conversion.
• Refer to Condensate Drain section for information how to install the
10.
condensate drain.
Remove plug from
collector box.
DO NOT DISCARD.
Unconverted Factory Trap Configuration
As Viewed in the Horizontal Right Orientation
Attach condensate trap
to collector box with
screw.
Install plug in open
port on collector box.
Horizontal Right Trap Configuration
Fig. 10 – Horizontal Right Trap Configuration
The condensate trap extends below the side of the casing in the
horizontal position. A minimum of 2-in. (51 mm) of clearance is
required between the casing side and the furnace platform for the trap to
extend out of the casing in the horizontal position. Allow at least 1/4-in.
per foot (20 mm per meter) of slope down.
The field-supplied, accessory horizontal drain trap grommet is ONLY
REQUIRED FOR DIRECT VENT APPLICATIONS. It it NOT
required for applications using single-pipe or ventilated combustion air
venting.
A11586
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in burst water pipes and/or
property damage.
If a condensate pump is installed, a plugged condensate drain or a failed
pump may cause the furnace to shut down. Do not leave the home
unattended during freezing weather without turning off water supply
and draining water pipes or otherwise protecting against the risk of
frozen pipes.
10
If alternate vent position
is required, loosen clamp
on inlet of vent elbow.
Remove trap from
collector box.
Slide relief tube in
stand-offs to adjust length.
Vent elbow shown in alternate
orientation. Tighten clamp on
inlet to vent elbow 15 lb.-in.
Align trap over middle and
right-hand port on collector box.
(Appearance May Vary)
NOTICE
!
CAUTION
!
A11278A
A11278B