Download Print this page

Omron H8PS-8AF Manual page 29

Cam positioner

Advertisement

Step Number Limit (f5)
With the H8PS, up to 10 steps can be set to turn the output ON/OFF
10 times for each cam. The number of steps that can be set,
however, can be restricted to prevent programming from being added
through operating mistakes. Settings can be made for all cams at
once or each cam individually. The default setting for the Step
Number Limit is 10 steps for all cams.
Example: Limiting the Number of Steps to 2 for All Cams
Collectively.
The maximum number of steps to be set is set using the F5 menu in
the Function Setting Mode.
Display for Collective Settings
PRG
CAM
STEP
The cam number can be set to a on the setting display to set all
cams at once. If the number of steps is displayed as "---" when the
cam number is a, the collective settings for all cams are disabled.
Example: Limiting the Number of Steps to 1 for Cam 3.
The maximum number of steps to be set is set using the F5 menu in
the Function Setting Mode.
Display for Individual Settings
PRG
STEP
CAM
Cam Protection (f6)
Cam programs can be write-protected. Use this setting to protect the
programs for only specific cam numbers. Protected cam numbers will
not be displayed in Programming Mode or Test Mode. Writing or
changing programs will not be possible. Protected cam numbers will
also not be displayed in Run Mode and cannot be checked. The
default settings are for no protection for all cams.
Example: Protecting Cam 3 with an 8-output Model
Cam protection is set using the F6 menu in the Function Setting
Mode.
Setting Display
Not lit (protected)
1
2
4
5
6
7
8
PRG
CAM
STEP
Set the cam number to a with the
CAM Keys
and set the
maximum number of steps to 2 with
the Angle Keys
. Press the
Key to write the setting to
WRITE
memory.
Set the cam number to 3 with the
CAM Keys
and set the
maximum number of steps to 1 with
the Angle Keys
. Press the
Key to write the setting to
WRITE
memory.
Set the cam number to be
protected (and not displayed) to 3
with the CAM Keys
and
then press the
Key. The
WRITE
output display will go out.
Bank Functions (f7/f8/f9)
The bank function is supported by 16-/32-output models. Banks
enable changing the entire cam program at once by switching bank
numbers (0 to 7).
Cam Program (Bank No. 7)
Cam Program (Bank No. 2)
Cam Program (Bank No. 1)
Cam Program (Bank No. 0)
Step 0
Step 1
Control output
(cam number)
ON angle OFF angle
ON angle
OFF angle
1
45°
90°
135°
225°
2
90°
135°
180°
32
90°
225°
270°
285°
In Run Mode or Test Mode, the start input must be turned OFF and
ON as shown in the following diagram in order to change banks.
Control the start input when changing banks.
Bank
Bank 0
specification
T4
ON
Start
input
OFF
T2
Bank 0
Operation
ON
RUN
output
OFF
Unstable region (outputs OFF)
T1: 225 ms max.
T2: 400 ms max.
T3: 20 ms min.
T4: 20 ms min.
Bank Enable/Disable (f7)
The default setting disables the bank function. To use banks, change
the setting using the F7 menu in the Function Setting Mode.
Setting Display
PRG
CAM
STEP
Bank Switching Method (f8)
The following methods can be used to switch the bank: the bank
inputs on the terminal block or the BANK Key on the front of the Cam
Positioner.
H8PS
Step 9
ON angle
OFF angle
270°
315°
---
---
315°
345°
Bank 1
Bank 2
T1
T2
T3
Bank 1
Bank 2
Enable or disable the bank function
with the ANGLE Keys
.
yes
no
(Enabled)
(Disabled)
29

Advertisement