Room Air Important; Minimum Clearance To Combustible Materials - Regency Cassic F2450M Owners & Installation Manual

Freestanding woodstove
Table of Contents

Advertisement

Room Air Important

For installation using room air for combustion,
remove knockout from the pedestal, and/or from
the bottom if using a heat shield.
Mobile home installations require the use of
outside air.
Minimum Clearance To
Combustible Materials
Please read the section below carefully as clearances depend on whether the airmate or the rear
heat deflector is installed on the stove.
Measurements "From Unit" are from the top plate of the stove to a side wall or to a corner, and from
the rear heat shield to a back wall.
Clearances may only be reduced by means approved by the regulatory authority.
Minimum ceiling height - 83" (2108mm)
NOTE: This clearance is also required for air space between the appliance and wall/ceiling.
NOTE: Be aware that local Codes and Regulations may override some clearances listed in this manual.
Check with your local inspector.
Residential Installation "C" Vent (Single Wall)
Unit
Medium F2450M
with Airmate
with Rear Deflector
Residential Close Clearance (To be installed with required pipe components)
When the stove is installed as a close clearance residential unit, a listed double wall connector is required from the stove collar to the ceiling level.
Unit
Medium F2450M
with Airmate 15" (381mm)
with Rear Deflector 15" (381mm)
Mobile Home Close Clearance (To be installed with required pipe components)
"C" Vent single wall pipe is not approved for Mobile Home installations. (Refer to Mobile Home Instructions.)
Unit
Medium F2450M
with Airmate
with Rear Deflector
On pedestal units there are two locations where
outside air may be adapted to the unit. If using
the bottom of the pedestal, do not remove knock-
out from the rear of the pedestal. Only remove
rear knockout if outside air will be brought in
from the rear.
On leg units outside air can only be brought in
from the bottom of the heat shield.
From Unit
A
B
16" (406mm)
9.5" (241mm)
16" (406mm)
11.5" (292mm) 8" (203mm)
From Unit
A
B
8" (203mm)
10" (254mm)
From Unit
A
B
15" (381mm)
8" (203mm)
15" (381mm)
10" (254mm)
Note: Once the knockout is removed
From Corner
C
D
8" (203mm)
28" (711mm)
28" (711mm)
From Corner
C
D
6" (152mm)
27" (686mm)
6" (152mm)
27" (686mm)
From Corner
C
D
6" (152mm)
27" (686mm)
6" (152mm)
27" (686mm)
F2450M Regency Freestanding Woodstove
installation
there are two tabs remaining.
Bend both tabs out for ease of
installation when attaching out-
side air.
B
E
A
D
F
From Flue Center-Line
E
F
16" (406mm)
20" (508mm)
18" (457mm)
20" (508mm)
From Flue Center-Line
E
F
14.5" (368mm)
18" (457mm)
16.5" (419mm)
18" (457mm)
From Flue Center-Line
E
F
14.5" (368mm)
18" (457mm)
16.5" (419mm)
18" (457mm)
F
C
C
|
9