Westinghouse WBRC 140F Series Installation & Start-Up Instructions page 42

Gas fired residential combi boiler floor mount
Hide thumbs Also See for WBRC 140F Series:
Table of Contents

Advertisement

SYSTEM CONTROL SETTINGS
MAXIMUM FLAME DETECTING VOLTAGE
PRE-PURGE TIME (Tp)
SAFETY TIME (IGNITING TIME) (Ts)
IGNITING INTERVAL TIME
POST-PURGE TIME (Tip)
OVER-HEATING 1,2,3 PROTECTION DETECTION TIME
PUMP 1 POST CIRCULATING TIME (T1pv)
PUMP 2 POST CIRCULATING TIME (T2pv)
HIGH AND LOW WATER LEVEL DETECTION TIME
HIGH AND LOW WATER LEVEL RECOVERY TIME
Table 20 – System Control Settings
2.5V
5 seconds
3.5 seconds
10 seconds
st
nd
2 minutes (1
: 1 minute, 2
<3 seconds
1 minute
1 minute
<6 seconds
<6 seconds
42
: 1 minute)
WHL-015 REV. 1.13.17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wbrc 199f seriesWbrclp140f

Table of Contents