Westinghouse WBRC 140F Series Installation & Start-Up Instructions page 38

Gas fired residential combi boiler floor mount
Hide thumbs Also See for WBRC 140F Series:
Table of Contents

Advertisement

Figure 25 – DHW Priority with Outdoor Reset, Boiler Primary Pump, and Recirculation
NOTES:
1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local
codes.
2. All closely spaced tees shall be within 4 pipe diameters center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees.
4. The minimum pipe size of DHW piping should be ¾" diameter and CH piping should be 1" in diameter.
5. Circulators are shown with isolation flanges. The alternative is standard flanges with full port ball valves. Purge valves can be used
with circulator flanges as an alternative.
6. Piping shown is Primary/Secondary. System flow (secondary loop) must be greater than the appliance's primary loop flow.
7. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
8. VERY IMPORTANT – Minimum flow rates outlined in this manual must be maintained through the heat exchanger to minimize short
cycling.
9. Each heating zone of a pump-based system has its own circulator with turns on when a zone thermostat calls for heat.
10. Unit is equipped with built-in primary pump for the heating loop. This pump is sized to insure proper flow rate through the
appliance heat exchanger and related piping. On long pipe runs, it is recommended to keep the pump at maximum speed (setting 3).
DO NOT lower it from the factory default.
11. To achieve 199,000 BTU/hr, install a Boiler Primary Pump. NOTE: RECOMMENDED PUMP: TACO 0013 or equivalent.
Boiler Primary Pump Instructions:
a. Install pump. Connect the pump to boiler terminal (2A max).
b. Go into installer menu and change 19:cb from 70 (default) to 100.