Step 2.3 Connecting the cables (assembly
cable)
Before
connecting
Correct
After
connecting
Correct
(Front view)
<Circular terminal>
AR
JC/KC
✴✴
✴✴
N(1)
1
Fasten the screws for the wire holders.
Model
(AR✴✴JC/KC✴✴)
Power cable
3G X 1.0 mm²,
(Indoor unit)
Indoor-to-Outdoor
3G X 1.0 mm²,
power cable
Type GL
Model
✴✴09/12✴✴
(AR✴✴HP/JP/KP/MP✴✴)
Power cable
3G X 1.0 mm²,
(Indoor unit)
Indoor-to-Outdoor
5G X 1.0 mm²,
power cable
Type GL
DB68-06031A-01_A5.indd 33
Control box
Upside down
Damaged
Non-circular
Correct
Upside down
Non-fitted
(Side view)
AR
HP/JP/KP/MP
✴✴
✴✴
(N)1 1
2
3
✴✴12✴✴
✴✴18/24✴✴
3G X 2.5 mm²,
H05VV-F
H05VV-F
3G X 2.5 mm²,
H07RN-F
H07RN-F
20A
25A
✴✴18✴✴LN/PF/SG
✴✴18✴✴RC
✴✴24✴✴
3G X 1.5 mm²,
3G X 2.5 mm²,
H05VV-F
H05VV-F
H05VV-F
3G X 2.5 mm²,
H07RN-F
5G X 1.5 mm²,
H07RN-F
H07RN-F
2 X 0.75 mm²,
H05RN-F
20 A
25A
25A
• When performing electrical and earthing works,
be sure to comply with the 'technical standards of
electrical installations' and the 'wiring regulations' in
the local regulations.
• Tighten the terminal block screw to 1.2-1.8 N•m
(1.2-1.8 kgf•cm).
NOTE
• Each wire is labelled with the corresponding
terminal number.
• Use shield cable (Category 5; less than 50pF/m) for
noisy environmental site.
• Power supply cords of parts of appliances
for outdoor use shall not be lighter than
polychloroprene sheathed flexible cord. (Code
designation IEC:60227 IEC53/CENELEC: H05VV-F,
IEC: 60245 IEC 66/CENELEC: H07RN-F, IEC: 60245
IEC 57/CENELEC: H05RN-F)
• Power & Communication cable shall not exceed
30m.
CAUTION
• For the terminal block wiring, use a wire with a
ring terminal socket only. Regular wires without
a ring terminal socket may become a hazard due
to overheating of the electrical contact during
installation.
• If you need to extend the pipe, be sure to
extend the cable, too. The maximum length
of each of the cable and pipe used should not
exceed 15 metres(✴✴09/12/18✴✴) and 20
metres(✴✴24✴✴).
• Do not connect two or more different cables to
extend the length. This connection may cause fire.
• Each circular terminal must match the size of its
corresponding screw in the terminal block.
• After connecting the cables, make sure that terminal
numbers on the indoor and outdoor units match.
• Ensure that power and communication cables are
separated, they must not be in the same cable.
WARNING
• Connect the wires firmly so that wires cannot be
pulled out easily. (If they are loose, it could cause
burn-out of the wires.)