Inspection Of Gas Nozzle Before Commissioning - Bentone BG 550 Installation And Maintenance Instruction

Table of Contents

Advertisement

4.8 Inspection of gas nozzle before
commissioning
The gas nozzle can easily be inspected by using the guides on the burner.
Proceed as follows:
1.
Ensure that no power is going to the burner. Switch off the main power
supply and disconnect the Euro plugs from the burner.
!
If the burner is directly connected, ensure that all components on
the burner are without power.
2.
Remove the cover plate from the fan housing.
3.
Undo the nut (D) to the nozzle assembly.
4.
Disconnect the ignition cable and ionisation cable for the gas nozzle.
5.
Ensure there is enough slack in the electrical cables to the valve
assembly and gas damper motor to pull out the burner body in the rear
position on the guides. If there is not enough slack the cables can be
disconnected.
6.
Undo the screw (B) on both sides.
7.
Pull out the burner on the guides.
8.
Undo the screw(s) (A) on the gas flange.
9.
Take out the gas nozzle.
10.
See section Gas nozzle
Re-assemble the burner in reverse order to that described above. When re-
assembling, make sure that the O-ring located between the gas nozzle and
the gas flange is in the correct position when the nozzle is re-fitted.
Service position
172 515 31
2018-01-15