Download Print this page
olympia electronics GR-290/WP/M Manual

olympia electronics GR-290/WP/M Manual

Waterproof self testing non-maintained emergency ceiling mounted luminaires

Advertisement

Quick Links

WATERPROOF SELF TESTING NON-MAINTAINED EMERGENCY CEILING MOUNTED LUMINAIRES
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (NiMh)
INSULATION BETWEEN SUPPLY & CONTROL TERMINALS
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGE TIME
MINIMUM DURATION
LIGHT SOURCE
EMERGENCY ILLUMINATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION
WEIGHT
GUARANTEE
GENERAL
This device is used indoors (ta 40 C) in
places where emergency luminaires are
needed. Each device must be permanently
connected to mains power supply. The
l u m i n a i r e s G R - 2 9 0 / W P / M a n d G R -
292/WP/M are suitable for corridors lighting
and the GR-291/WP/M and GR-293/WP/M
for open area lighting. In normal operation
the battery is charging. In case of a mains
power supply failure, the device enters
emergency mode and the illumination LED
turns on. When the mains power supply is
r e s t o r e d t h e d e v i c e t u r n s t o n o r m a l
operation.
INSTALLATION
To install the luminaire follow the installation
instructions οn page 3.
Battery Charging
The
battery
charging
controlled. In this case, is achieved the
perfect battery maintenance , as well as the
elongation of its duration. When the battery
has completely charged, it charges with a
maintenance current.
Page 1 from 6
GR-290/WP/M GR-291/WP/M GR-292/WP/M GR-293/WP/M
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Thank you for your trust in our products
Olympia Electronics - European manufacturer
o
is
completely
(for LED MODULE specifications see page 5)
220-240V AC / 50-60Hz
4.3W / 4.7 VA
4.8V/1.2Ah
Basic insulation
Deep discharge and overcharge protection
Charge, lamp fault, battery fault
24 hours
1.5 hour
1 white power LED
300lm
IP65
5 to 40 C
Up to 95%
ABS/PC
Ø125 x 65 mm
442gr.
3 years (1 year for the battery)
Battery Cut-off
The device in this operation when the mains
power supply fails and battery has lost its
energy. During this operation the device
enters the idle state and battery consumption
is negligible, in order to be protected from
deep discharge.
Automatic Operational Test
It is conducted automatically every 15 days. In
order to be performed, the mains power
supply and the battery should be connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the device's back up operation
and emergency duration. The BATTERY
FAULT LED blinks during the measurement,
indicating this process to the user. This test is
conducted automatically every six months. In
order to be performed, the mains power
supply and the battery should be connected
and fully charged. If the battery is not fully
charged, the test is postponed until the
battery is completely charged. If during this
test, the autonomy is less than the nominal
then
the
battery
continuously
and
3 hours
150lm
o
fault
led
turned
the
battery
must
923293004_09_004
on
be

Advertisement

loading

Summary of Contents for olympia electronics GR-290/WP/M

  • Page 1 WATERPROOF SELF TESTING NON-MAINTAINED EMERGENCY CEILING MOUNTED LUMINAIRES TECHNICAL CHARACTERISTICS (for LED MODULE specifications see page 5) GR-290/WP/M GR-291/WP/M GR-292/WP/M GR-293/WP/M OPERATION VOLTAGE 220-240V AC / 50-60Hz 4.3W / 4.7 VA MAXIMUM POWER CONSUMPTION BATTERY (NiMh) 4.8V/1.2Ah INSULATION BETWEEN SUPPLY & CONTROL TERMINALS...
  • Page 2: Labeling Explanation

    replaced. supports inhibit or rest mode, you should Back Up Operation know that these commands can be cancelled The autonomous duration of battery during only during normal mode (ie. emergency mode is at least the one that is emergency). For installation refer to step 3 of stated list technical...
  • Page 3: Installation Instructions

    INSTALLATION INSTRUCTIONS Cable entry hole 1 Untighten the screw but do not remove it and pull up the reflector. 2 Always use in any case round mains cable, with a diameter of 5-10mm (H05RN-F type 2x1mm² or any other type, at least equal to it’s mechanical and electrical properties). ATTENTION!! The cable must not be deformed in any way (This requirement is important to ensure the ΙΡ...
  • Page 4: Surface Mounting

    ATTENTION!! Especially for the GR-290/WP/M and GR-292/WP/M luminaire installation on the ceiling you must align the base with the indications on the luminaire’s base (Figure 5).
  • Page 5 GR-290/WP/M, GR-292/WP/M Corridor lighting LAMP BATT. CHARGE LAMP BATT. FAULT CHARGE FAULT ATTENTION!!! Lamp fault During installation follow this light direction. indication LED GR-291/WP/M, GR-293/WP/M Battery Battery charge fault indication indication Open area LAMP BATT. LAMP BATT. CHARGE CHARGE FAULT...
  • Page 6: Warranty

    Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Gr-291/wp/mGr-292/wp/mGr-293/wp/m