8 Configuration
7. Select [Edit].
8. Select the parameter group System and device control system > Inverter >
Configuration of the static voltage stability.
9. Set the parameter Operating mode of the static voltage stability to the desired operating
mode. When doing so, note that for "Q on Demand 24/7", none of the operating modes with
cos Phi may be selected.
10. Select the parameter Operating mode of the static voltage stability for Q on demand
and set this to the desired operating mode also.
11. Depending on the selection of the static voltage stability operating mode, set the parameters
associated with the selected operating mode (e.g. the reactive power / voltage characteristic
curve Q(V) with or without data points or the reactive power setpoint Q).
12. Click on [Save].
8.6

Reducing the Attenuation of Ripple Control Signals

By setting certain parameters, the attenuation of three-phase parallel ripple control frequencies
ranging from 1000 Hz to 1100 Hz can be avoided. The parameters must only be set in
consultation with the responsible grid operator.
The basic procedure for changing operating parameters is explained in another section (see
Section 8.3 "Changing Operating Parameters", page 46).
Requirements:
☐ The firmware version of the inverter must be at least 2.81.07.R.
Procedure:
• Set the following parameters:
SMA Data/
RS485
RplDet-NBS-Gain Ripple control signal detection, am-
RplDet-NBS-
Damp
RplDet-NBS-Hz
8.7

Setting SMA ShadeFix

For partially shaded PV modules, you should set the interval at which the inverter is to optimize the
MPP of the PV system. If you do not want to use SMA OptiTrac Global Peak feature, you can
deactivate the feature.
48
STP15-25TL-30-BE-en-17
Definition
plification of narrow-band backup
Ripple control signal detection, at-
tenuation of narrow-band backup
Ripple control signal detection, fre-
quency of the narrow-band backup
SMA Solar Technology AG
Unit
Range Value to be set
V/A
0 to -10 -9
p.u.
-
0.1
Hz
1000
Must be specified
to
by the grid oper-
1100
ator
Operating manual